22-62
Broken Belt Delay
Value:
0 - 600 s
10 s
Function:
Sets the time during which the broken belt
conditions must be active before carrying out
the action selected in
Broken Belt Function,
par. 22-60.
22-75
Short Cycle Protection
Value:
Disabled
[0]
Enabled
[1]
Function:
Disabled
[0]: Timer set in
Interval Between
Starts
, par. 22-76 is disabled.
Enabled
[1]: Timer set in
Interval between
Starts
, par. 22-76 is enabled.
22-76
Interval Between Starts
Value:
0 - 3,600 s
0 s
Function:
Sets the time desired as minimum time be-
tween two starts. Any normal start command
(Start/Jog/Freeze) will be disregarded until
the timer has expired.
22-77
Minimum Run Time
Value:
0 - par. 22-76
0 s
Function:
Sets the time desired as min. run time after a
normal start command (Start/Jog/Freeze).
Any normal stop command will be disregarded
until the set time has expired. The timer will
start counting after a normal start command
(Start/Jog/Freeze).
The timer will be overridden by a coast (in-
verse) or an external interlock command.