Stop
[2]
Jogging
[3]
Max. speed
[4]
Stop and trip
[5]
Function:
Select the timeout function. The function set
in par. 6-01 will be activated if the input signal
on terminal 53 or 54 is below 50% of the value
in par. 6-10, par. 6-12, par. 6-20 or par. 6-22
for a time period defined in par. 6-00. If sev-
eral timeouts occur simultaneously, the ad-
justable frequency drive prioritizes the time-
out functions as follows:
1.
Par. 6-01
Live Zero Timeout Function
2.
Par. 8-04
Control Word Timeout
Function
The output frequency of the adjustable fre-
quency drive can be:
•
[1] frozen at the present value
•
[2] overruled to stop
•
[3] overruled to jog speed
•
[4] overruled to max. speed
•
[5] overruled to stop with subse-
quent trip
If you select set-up 1-4, par. 0-10,
Active Set-
up
, must be set to
Multi Set-up
, [9].
This parameter cannot be adjusted while the
motor is running.
6-10
Terminal 53 Low Voltage
Value:
0.00 - par. 6-11
0.07 V
Function:
Enter the low voltage value. This analog input
scaling value should correspond to the low
reference/feedback value set in par. 6-14.
6-11
Terminal 53 High Voltage
Value:
Par. 6-10 to 10.0 V
10.0 V
Function:
Enter the high voltage value. This analog input
scaling value should correspond to the high
reference/feedback value set in par. 6-15.
6-14
Terminal 53 Low Ref./Feedb.
Value
Value:
-1000000.000 to par. 6-15
0.000 Unit
Function:
Enter the analog input scaling value that cor-
responds to the low voltage/low current set in
par. 6-10 and 6-12.
6. How to program the adjustable frequency
drive
VLT
®
HVAC Drive Instruction Manual
86
MG.11.A4.22
-
VLT
®
is a registered Danfoss trademark
6