Above Speed, high
[17]
Out of Feedb. Range
[18]
Below Feedback, low
[19]
Above Feedback, high
[20]
Thermal Warning
[21]
Reverse
[25]
Bus OK
[26]
Torque Limit & Stop
[27]
Brake, No Warning
[28]
Brake Ready, No Fault
[29]
Brake Fault (IGBT)
[30]
External Interlock
[35]
Control Word Bit 11
[36]
Control Word Bit 12
[37]
Out of Ref. Range
[40]
Below Reference, low
[41]
Above Ref. high
[42]
Bus ctrl
[45]
Bus ctrl, 1 if timeout
[46]
Bus ctrl, 0 if timeout
[47]
Comparator 0
[60]
Comparator 1
[61]
Comparator 2
[62]
Comparator 3
[63]
Comparator 4
[[64]]
Comparator 5
[[65]]
Logic Rule 0
[70]
Logic Rule 1
[71]
Logic Rule 2
[72]
Logic Rule 3
[73]
Logic Rule 4
[[74]]
Logic Rule 5
[[75]]
SL Digital Output A
[80]
SL Digital Output B
[81]
SL Digital Output B
[82]
SL Digital Output D
[83]
SL Digital Output E
[84]
SL Digital Output F
[85]
No Alarm
[160]
Running Reverse
[161]
Local Ref. Active
[165]
Remote Ref. Active
[166]
Start Cmd. Active
[167]
Drive in Hand Mode
[168]
Drive in Auto Mode
[169]
Clock Fault
[180]
Prev. Maintenance
[181]
No-Flow
[190]
Dry Pump
[191]
End of Curve
[[192]]
Sleep Mode
[193]
Broken Belt
[194]
Bypass Valve Control
[195]
Cascade Pump1
[211]
Cascade Pump2
[212]
Cascade Pump3
[213]
Fire Mode Active
[[220]]
Fire Mode Coast
[[221]]
Fire Mode Was Active
[[222]]
Alarm, Trip-locked
[[223]]
Bypass Mode Active
[[224]]
Function:
Select options to define the function of the re-
lays.
The selection of each mechanical relay is re-
alized in an array parameter.
6-00
Live Zero Timeout Time
Value:
1 - 99 s
10s
Function:
Enter the Live Zero Timeout time period. Live
Zero Timeout Time is active for analog inputs,
i.e., terminal 53 or terminal 54, and is alloca-
ted to current and used as reference or feed-
back sources. If the reference signal value
associated with the selected current input falls
below 50% of the value set in par. 6-10, par.
6-12, par. 6-20 or par. 6-22 for a time period
longer than the time set in par. 6-00, the func-
tion selected in par. 6-01 will be activated.
6-01
Live Zero Timeout Function
Value:
Off
[0]
Freeze output
[1]
VLT
®
HVAC Drive Instruction Manual
6. How to program the adjustable frequency
drive
MG.11.A4.22 - VLT
®
is a registered Danfoss trademark
85
6