UL Compliance
VLT
HVAC
Bussmann Bussmann Bussmann
SIBA
Littel fuse
Ferraz-
Shawmut
Ferraz-
Shawmut
200-240 V
kW
Type RK1 Type J
Type T
Type RK1
Type RK1
Type CC
Type RK1
K25-1K1 KTN-R10
JKS-10
JJN-10
5017906-010 KLN-R10
ATM-R10
A2K-10R
1K5
KTN-R15
JKS-15
JJN-15
5017906-015 KLN-R15
ATM-R15
A2K-15R
2K2
KTN-R20
JKS-20
JJN-20
5012406-020 KLN-R20
ATM-R20
A2K-20R
3K0
KTN-R25
JKS-25
JJN-25
5012406-025 KLN-R25
ATM-R25
A2K-25R
3K7
KTN-R30
JKS-30
JJN-30
5012406-030 KLN-R30
ATM-R30
A2K-30R
5K5
KTN-R50
JKS-50
JJN-50
5012406-050 KLN-R50
-
A2K-50R
7K5
KTN-R50
JKS-60
JJN-60
5012406-050 KLN-R60
-
A2K-50R
11K
KTN-R60
JKS-60
JJN-60
5014006-063 KLN-R60
A2K-60R
15K
KTN-R80
JKS-80
JJN-80
5014006-080 KLN-R80
A2K-80R
18K5
KTN-R125 JKS-150
JJN-125
2028220-125 KLN-R125
A2K-125R
22K
KTN-R125 JKS-150
JJN-125
2028220-125 KLN-R125
A2K-125R
30K
FWX-150
-
-
2028220-150 L25S-150
A25X-150
37K
FWX-200
-
-
2028220-200 L25S-200
A25X-200
45K
FWX-250
-
-
2028220-250 L25S-250
A25X-250
Table 4.3: UL fuses 200-240 V
VLT
HVAC
Bussmann Bussmann Bussmann
SIBA
Littel fuse
Ferraz-
Shawmut
Ferraz-
Shawmut
380-500 V, 525-600
kW
Type RK1
Type J
Type T
Type RK1
Type RK1
Type CC
Type RK1
11K
KTS-R40
JKS-40
JJS-40
5014006-040 KLS-R40
-
A6K-40R
15K
KTS-R40
JKS-40
JJS-40
5014006-040 KLS-R40
-
A6K-40R
18K
KTS-R50
JKS-50
JJS-50
5014006-050 KLS-R50
-
A6K-50R
22K
KTS-R60
JKS-60
JJS-60
5014006-063 KLS-R60
-
A6K-60R
30K
KTS-R80
JKS-80
JJS-80
2028220-100 KLS-R80
-
A6K-80R
37K
KTS-R100 JKS-100
JJS-100
2028220-125 KLS-R100
A6K-100R
45K
KTS-R125 JKS-150
JJS-150
2028220-125 KLS-R125
A6K-125R
55K
KTS-R150 JKS-150
JJS-150
2028220-160 KLS-R150
A6K-150R
75K
FWH-220
-
-
2028220-200 L50S-225
A50-P225
90K
FWH-250
-
-
2028220-250 L50S-250
A50-P250
Table 4.4: UL fuses 380-600 V
KTS fuses from Bussmann may substitute for KTN in 240 V adjustable frequency drives.
FWH fuses from Bussmann may substitute for FWX in 240 V adjustable frequency drives.
KLSR fuses from LITTEL FUSE may substitute for KLNR fuses in 240 V adjustable fre-
quency drives.
L50S fuses from LITTEL FUSE may substitute for L50S fuses in 240 V adjustable fre-
quency drives.
A6KR fuses from FERRAZ SHAWMUT may substitute for A2KR in 240 V adjustable fre-
quency drives.
A50X fuses from FERRAZ SHAWMUT may substitute for A25X in 240 V adjustable fre-
quency drives.
VLT
®
HVAC Drive Instruction Manual
4. Electrical installation
MG.11.A4.22 - VLT
®
is a registered Danfoss trademark
29
4