Normal overload 110% for 1 minute
Adjustable frequency drive
Typical Shaft Output [kW]
P11K
11
P15K
15
P18K
18.5
P22K
22
P30K
30
P37K
37
P45K
45
P55K
55
P75K
75
P90K
90
Typical Shaft Output [HP] at 460 V
15
20
25
30
40
50
60
75
100
125
IP 20
IP 21
B1
B1
B1
B2
B2
C1
C1
C1
C2
C2
IP 55
B1
B1
B1
B2
B2
C1
C1
C1
C2
C2
IP 66
B1
B1
B1
B2
B2
C1
C1
C1
Output current
Continuous
(3 x 380-440 V) [A]
24
32
37.5
44
61
73
90
106
147
177
Intermittent
(3 x 380-440 V) [A]
26.4 35.2 41.3 48.4 67.1 80.3
99
117
162
195
Continuous
(3 x 440-480 V) [A]
21
27
34
40
52
65
80
105
130
160
Intermittent
(3 x 440-480 V) [A]
23.1 29.7 37.4
44
61.6 71.5
88
116
143
176
Continuous kVA
(400 V AC) [kVA]
16.6 22.2
26
30.5 42.3 50.6 62.4 73.4 102
123
Continuous kVA
(460 V AC) [kVA]
16.7 21.5 27.1 31.9 41.4 51.8 63.7 83.7 104
128
Max. cable size:
(line, motor, brake)
[[mm
2
/
AWG]
2)
10/7
35/2
50/1/0
104
128
Max. input current
Continuous
(3 x 380-440 V) [A]
22
29
34
40
55
66
82
96
133
161
Intermittent
(3 x 380-440 V) [A]
24.2 31.9 37.4
44
60.5 72.6 90.2 106
146
177
Continuous
(3 x 440-480 V) [A]
19
25
31
36
47
59
73
95
118
145
Intermittent
(3 x 440-480 V) [A]
20.9 27.5 34.1 39.6 51.7 64.9 80.3 105
130
160
Max. pre-fuses
1)
[A]
63
63
63
63
80
100
125 160
250
250
Environment
Estimated power loss
at rated max. load [W]
4)
278 392
465
525
739
698
843 1083 1384 1474
Weight enclosure IP 20
[kg]
Weight enclosure IP 21
[kg]
23
23
23
27
27
45
45
45
65
65
Weight enclosure IP 55
[kg]
23
23
23
27
27
45
45
45
65
65
Weight enclosure IP 66
[kg]
23
23
23
27
27
45
45
45
-
-
Efficiency
3)
0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98
0.99
VLT
®
HVAC Drive Instruction Manual
8. Specifications
MG.11.A4.22 - VLT
®
is a registered Danfoss trademark
143