also increases the time delay through the fil-
ter.
This parameter cannot be adjusted while the
motor is running.
6-27
Terminal 54 Live Zero
Value:
Disabled
[0]
Enabled
[1]
Function:
This parameter makes it possible to disable
Live Zero monitoring. For example, it is to be
used if the analog outputs are used as part of
a decentral I/O system (such as when they are
not part of any adjustable frequency drive re-
lated control functions, but feeding a building
management system with data)
6-50
Terminal 42 Output
Value:
No operation
[0]
Output frequency
[100]
Reference
[101]
Feedback
[102]
Motor current
[103]
Torque rel to lim
[104]
Torque rel to rated
[105]
Power
[106]
Speed
[107]
Torque
[108]
Ext. closed-loop 1
[113]
Ext. closed-loop 2
[114]
Ext. closed-loop 3
[115]
Output freq. 4-20 mA
[130]
Reference 4-20 mA
[131]
Feedback 4-20 mA
[132]
Motor cur. 4-20 mA
[133]
Torque % lim. 4-20 mA
[134]
Torque % nom 4-20 mA
[135]
Power 4-20 mA
[136]
Speed 4-20 mA
[137]
Torque 4-20 mA
[138]
Bus ctrl. 0-20 mA
[139]
Bus ctrl. 4-20 mA
[140]
Bus ctrl. 0-20 mA, timeout
[141]
Bus ctrl. 4-20 mA, timeout
[142]
Ext. Closed-loop 1, 4-20 mA
[[143]]
Ext. Closed-loop 2, 4-20 mA
[[144]]
Ext. Closed-loop 3, 4-20 mA
[[145]]
Function:
Select the function of terminal 42 as an analog
current output.
6-51
Terminal 42 Output Min Scale
Value:
0.00 – 200%
0%
Function:
Scale the minimum output of the selected an-
alog signal at terminal 42, as a percentage of
the maximum signal value. For example, if 0
mA (or 0 Hz) is desired at 25% of the maxi-
mum output value, program it to 25%. Scaling
values up to 100% can never be higher than
the corresponding setting in par. 6-52.
6-52
Terminal 42 Output Max
Scale
Value:
0.00 – 200%
100%
Function:
Scale the maximum output of the selected an-
alog signal at terminal 42. Set the value to the
maximum value of the current signal output.
Scale the output to give a current lower than
20 mA at full scale, or 20 mA at an output be-
6. How to program the adjustable frequency
drive
VLT
®
HVAC Drive Instruction Manual
88
MG.11.A4.22
-
VLT
®
is a registered Danfoss trademark
6