Function:
Select
Input
[0] to define terminal 27 as a dig-
ital input.
Select
Output
[1] to define terminal 27 as a
digital output.
This parameter cannot be adjusted while the
motor is running.
5-02
Terminal 29 Mode
Value:
Input
[0]
Output
[1]
Function:
Select
Input
[0] to define terminal 29 as a dig-
ital input.
Select
Output
[1] to define terminal 29 as a
digital output.
This parameter cannot be adjusted while the
motor is running.
5-12
Terminal 27 Digital Input
Value:
Coast Inverse
[2]
Function:
Same options and functions as par. 5-1*
Dig-
ital Inputs
, except for
Pulse input
.
5-13
Terminal 29 Digital Input
Value:
Jog
[14]
Function:
Same options and functions as par. 5-1*
Dig-
ital Inputs
.
5-14
Terminal 32 Digital Input
Value:
No Operation
[0]
Function:
Same options and functions as par. 5-1*
Dig-
ital Inputs
, except for
Pulse input
.
5-15
Terminal 33 Digital Input
Value:
No Operation
[0]
Function:
Same options and functions as par. 5-1*
Dig-
ital Inputs
.
5-40
Function Relay
Array [8]
(Relay 1 [0], Relay 2 [1],
Relay 7 [6], Relay 8 [7],
Relay 9 [8])
Value:
No Operation
[0]
Control Ready
[1]
Drive Ready
[2]
Drive Ready/Remote
[3]
Stand-by/No Warning
[4]
Running
[5]
Running/No Warning
[6]
Run on Ref./No Warning
[8]
Alarm
[9]
Alarm or Warning
[10]
At Torque Limit
[11]
Out of Current Range
[12]
Below Current, low
[13]
Above Current, high
[14]
Out of Speed Range
[15]
Below Speed, low
[16]
6. How to program the adjustable frequency
drive
VLT
®
HVAC Drive Instruction Manual
84
MG.11.A4.22
-
VLT
®
is a registered Danfoss trademark
6