8-13 Configurable Status Word STW
Option:
Function:
1 indicates that the terminal is high.
[13] T29 DI status. The bit indicates the status of terminal 29.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
[14] T32 DI status. The bit indicates the status of terminal 32.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
[15] T33 DI status. The bit indicates the status of terminal 33.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
[16] T37 DI status
The bit indicates the status of terminal 37.
0 indicates terminal 37 is low (Safe Torque
stop).
1 indicates terminal 37 is high (normal).
[21] Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the motor,
the frequency converter, the brake resistor,
or the thermistor.
[30] Brake fault
(IGBT)
Output is logic 1 when the brake IGBT is
short-circuited. Use this function to protect
the frequency converter if there is a fault
on the brake modules. Use the output/relay
to cut out the main voltage from the
frequency converter.
[40] Out of ref.
range
[60] Comparator 0 See parameter group
13-1* Comparators
. If
comparator 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[61] Comparator 1 See parameter group
13-1* Comparators
. If
comparator 1 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[62] Comparator 2 See parameter group
13-1* Comparators
. If
comparator 2 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[63] Comparator 3 See parameter group
13-1* Comparators
. If
comparator 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[64] Comparator 4 See parameter group
13-1* Comparators
. If
comparator 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[65] Comparator 5 See parameter group
13-1* Comparators
. If
comparator 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[70] Logic Rule 0
See parameter group
13-4* Logic Rules
. If
logic rule 0 is evaluated as TRUE, the output
goes high. Otherwise, it is low.
[71] Logic Rule 1
See parameter group
13-4* Logic Rules
. If
logic rule 1 is evaluated as TRUE, the output
goes high. Otherwise, it is low.
[72] Logic Rule 2
See parameter group
13-4* Logic Rules
. If
logic rule 2 is evaluated as TRUE, the output
goes high. Otherwise, it is low.
8-13 Configurable Status Word STW
Option:
Function:
[73] Logic Rule 3
See parameter group
13-4* Logic Rules
. If
logic rule 3 is evaluated as TRUE, the output
goes high. Otherwise, it is low.
[74] Logic Rule 4
See parameter group
13-4* Logic Rules
. If
logic rule 4 is evaluated as TRUE, the output
goes high. Otherwise, it is low.
[75] Logic Rule 5
See parameter group
13-4* Logic Rules
. If
logic rule 5 is evaluated as TRUE, the output
goes high. Otherwise, it is low.
[80] SL Digital
Output A
See
parameter 13-52 SL Controller Action
. The
output goes high whenever the smart logic
action
[38] Set digital out A high
is executed.
The output goes low whenever the smart
logic action
[32] Set digital out A low
is
executed.
[81] SL Digital
Output B
See
parameter 13-52 SL Controller Action
. The
input goes high whenever the smart logic
action
[39] Set digital out B high
is executed.
The input goes low whenever the smart
logic action
[33] Set digital out B low
is
executed.
[82] SL Digital
Output C
See
parameter 13-52 SL Controller Action
. The
input goes high whenever the smart logic
action
[40] Set digital out C high
is executed.
The input goes low whenever the smart
logic action
[34] Set digital out C low
is
executed.
[83] SL Digital
Output D
See
parameter 13-52 SL Controller Action
. The
input goes high whenever the smart logic
action
[41] Set digital out D high
is executed.
The input goes low whenever the smart
logic action
[35] Set digital out D low
is
executed.
[84] SL Digital
Output E
See
parameter 13-52 SL Controller Action
. The
input goes high whenever the smart logic
action
[42] Set digital out E high
is executed.
The input goes low whenever the smart
logic action
[36] Set digital out E low
is
executed.
[85] SL Digital
Output F
See
parameter 13-52 SL Controller Action
. The
input goes high whenever the smart logic
action
[43] Set digital out F high
is executed.
The input goes low whenever the smart
logic action
[37] Set digital out F low
is
executed.
Parameter Descriptions
Programming Guide
MG11CE02