5-19 Terminal 37 Safe Stop
Use this parameter to configure the Safe Torque Off functionality.
A warning message makes the frequency converter coast the
motor and enables the automatic restart. An alarm message
makes the frequency converter coast the motor and requires a
manual restart (via a fieldbus, Digital I/O, or by pressing [RESET]
on the LCP). When the
VLT
®
PTC Thermistor Card MCB 112
is
mounted, configure the PTC options to get the full benefit from
the alarm handling.
Option:
Function:
converter continues without manual
reset, unless a digital input set to
[80] PTC Card 1
is still enabled.
[6]
PTC 1 & Relay A This option is used when the PTC
option gates with a stop key through
a safety relay to terminal 37. Coasts
frequency converter when Safe
Torque Off is activated. Manual reset
from LCP, digital input, or fieldbus.
[7]
PTC 1 & Relay
W
This option is used when the PTC
option gates with a stop key through
a safety relay to terminal 37. Coasts
frequency converter when Safe
Torque Off is activated (terminal 37
off). When safe-stop circuit is re-
established, the frequency converter
continues without manual reset,
unless a digital input set to
[80] PTC
Card 1
is still enabled.
[8]
PTC 1 & Relay
A/W
This option makes it possible to use
a combination of Alarm and Warning.
[9]
PTC 1 & Relay
W/A
This option makes it possible to use
a combination of Alarm and Warning.
NOTICE
Options
[4] PTC 1 Alarm
to
[9] PTC 1 & Relay W/A
are only
available when the MCB 112 is connected.
NOTICE
Selecting
Auto Reset/Warning
enables automatic restart
of the frequency converter.
Function
Num
ber
PTC
Relay
No Function
[0]
-
-
Safe Torque Off
Alarm
[1]*
-
Safe Torque Off
[A68]
Safe Torque Off
Warning
[3]
-
Safe Torque Off
[W68]
PTC 1 Alarm
[4]
PTC 1 Safe Torque
Off [A71]
-
PTC 1 Warning
[5]
PTC 1 Safe Torque
Off [W71]
-
PTC 1 & Relay A
[6]
PTC 1 Safe Torque
Off [A71]
Safe Torque Off
[A68]
PTC 1 & Relay W
[7]
PTC 1 Safe Torque
Off [W71]
Safe Torque Off
[W68]
PTC 1 & Relay A/W [8]
PTC 1 Safe Torque
Off [A71]
Safe Torque Off
[W68]
PTC 1 & Relay W/A [9]
PTC 1 Safe Torque
Off [W71]
Safe Torque Off
[A68]
Table 3.11 Overview of Functions, Alarms, and Warnings
W means warning and A means alarm. For further information, see
Alarms and Warnings in the Troubleshooting section in the Design
Guide or the Operating Instructions.
A dangerous failure related to Safe Torque Off issues
Alarm
72 Dangerous Failure
.
Refer to
3.7.3 5-3* Digital Outputs
Parameters for configuring the output functions for the
output terminals. The 2 solid-state digital outputs are
common for terminals 27 and 29. Set the I/O function for
terminal 27 in
parameter 5-01 Terminal 27 Mode
and set the
I/O function for terminal 29 in
. These parameters cannot be adjusted while the
motor is running.
The digital outputs can be programmed
with these functions:
[0]
No operation
Default for all digital outputs and relay
outputs.
[1]
Control ready
The control board receives supply voltage.
[2]
Drive ready
The frequency converter is ready for
operation and applies a supply signal on
the control board.
[3]
Drive ready /
remote
control
The frequency converter is ready for
operation and is in
Auto On
mode.
[4]
Stand-by / no
warning
The frequency converter is ready for
operation. No start or stop command is
given (start/disable). There are no
warnings.
[5]
Running
The motor is running.
Parameter Descriptions
Programming Guide
MG11CE02
Danfoss A/S © 03/2015 All rights reserved.
73
3