25-40 Ramp Down Delay
10 s
All set-ups
TRUE
-1
Uint16
25-41 Ramp Up Delay
2 s
All set-ups
TRUE
-1
Uint16
25-42 Staging Threshold
ExpressionLimit
All set-ups
TRUE
0
Uint8
25-43 Destaging Threshold
ExpressionLimit
All set-ups
TRUE
0
Uint8
25-44 Staging Speed [RPM]
0 RPM
All set-ups
TRUE
67
Uint16
25-45 Staging Speed [Hz]
0 Hz
All set-ups
TRUE
-1
Uint16
25-46 Destaging Speed [RPM]
0 RPM
All set-ups
TRUE
67
Uint16
25-47 Destaging Speed [Hz]
0 Hz
All set-ups
TRUE
-1
Uint16
25-5* Alternation Settings
25-50 Lead Pump Alternation
[0] Off
All set-ups
TRUE
-
Uint8
25-51 Alternation Event
[0] External
All set-ups
TRUE
-
Uint8
25-52 Alternation Time Interval
24 h
All set-ups
TRUE
74
Uint16
25-53 Alternation Timer Value
0 N/A
All set-ups
TRUE
0
VisStr[7]
25-54 Alternation Predefined Time
ExpressionLimit
All set-ups
TRUE
0
TimeOfDay-
WoDate
25-55 Alternate if Load < 50%
[1] Enabled
All set-ups
TRUE
-
Uint8
25-56 Staging Mode at Alternation
[0] Slow
All set-ups
TRUE
-
Uint8
25-58 Run Next Pump Delay
0.1 s
All set-ups
TRUE
-1
Uint16
25-59 Run on Mains Delay
0.5 s
All set-ups
TRUE
-1
Uint16
25-8* Status
25-80 Cascade Status
0 N/A
All set-ups
TRUE
0
VisStr[25]
25-81 Pump Status
0 N/A
All set-ups
TRUE
0
VisStr[25]
25-82 Lead Pump
0 N/A
All set-ups
TRUE
0
Uint8
25-83 Relay Status
0 N/A
All set-ups
TRUE
0
VisStr[4]
25-84 Pump ON Time
0 h
All set-ups
TRUE
74
Uint32
25-85 Relay ON Time
0 h
All set-ups
TRUE
74
Uint32
25-86 Reset Relay Counters
[0] Do not reset
All set-ups
TRUE
-
Uint8
25-9* Service
25-90 Pump Interlock
[0] Off
All set-ups
TRUE
-
Uint8
25-91 Manual Alternation
0 N/A
All set-ups
TRUE
0
Uint8
5.1.24 26-** Analog I / O Option MCB 109
Param
eter #
Parameter description
Default value
4 set-up
Change during
operation
Conversion
index
Type
26-0* Analog I/O Mode
26-00 Terminal X42/1 Mode
[1] Voltage
All set-ups
TRUE
-
Uint8
26-01 Terminal X42/3 Mode
[1] Voltage
All set-ups
TRUE
-
Uint8
26-02 Terminal X42/5 Mode
[1] Voltage
All set-ups
TRUE
-
Uint8
26-1* Analog Input X42/1
26-10 Terminal X42/1 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
26-11 Terminal X42/1 High Voltage
10 V
All set-ups
TRUE
-2
Int16
26-14 Term. X42/1 Low Ref./Feedb. Value
0 N/A
All set-ups
TRUE
-3
Int32
26-15 Term. X42/1 High Ref./Feedb. Value
100 N/A
All set-ups
TRUE
-3
Int32
26-16 Term. X42/1 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
26-17 Term. X42/1 Live Zero
[1] Enabled
All set-ups
TRUE
-
Uint8
26-2* Analog Input X42/3
26-20 Terminal X42/3 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
26-21 Terminal X42/3 High Voltage
10 V
All set-ups
TRUE
-2
Int16
26-24 Term. X42/3 Low Ref./Feedb. Value
0 N/A
All set-ups
TRUE
-3
Int32
26-25 Term. X42/3 High Ref./Feedb. Value
100 N/A
All set-ups
TRUE
-3
Int32
26-26 Term. X42/3 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
26-27 Term. X42/3 Live Zero
[1] Enabled
All set-ups
TRUE
-
Uint8
26-3* Analog Input X42/5
Parameter Lists
Programming Guide
MG11CE02