10-11 Process Data Config Write
Option:
Function:
[351]
Ramp 2 Ramp Up Time
[352]
Ramp 2 Ramp Down Time
[380]
Jog Ramp Time
[381]
Quick Stop Ramp Time
[411]
Motor Speed Low Limit [RPM]
[412]
Motor Speed Low Limit [Hz]
[413]
Motor Speed High Limit [RPM]
[414]
Motor Speed High Limit [Hz]
[416]
Torque Limit Motor Mode
[417]
Torque Limit Generator Mode
[553]
Term. 29 High Ref./Feedb. Value
[558]
Term. 33 High Ref./Feedb. Value
[590]
Digital & Relay Bus Control
[593]
Pulse Out #27 Bus Control
[595]
Pulse Out #29 Bus Control
[597]
Pulse Out #X30/6 Bus Control
[615]
Terminal 53 High Ref./Feedb. Value
[625]
Terminal 54 High Ref./Feedb. Value
[653]
Terminal 42 Output Bus Control
[663]
Terminal X30/8 Output Bus Control
[673]
Terminal X45/1 Bus Control
[683]
Terminal X45/3 Bus Control
[890]
Bus Jog 1 Speed
[891]
Bus Jog 2 Speed
[894]
Bus Feedback 1
[895]
Bus Feedback 2
[896]
Bus Feedback 3
[1680] Fieldbus CTW 1
[1682] Fieldbus REF 1
[1685] FC Port CTW 1
[1686] FC Port REF 1
10-12 Process Data Config Read
Option: Function:
Select the process read data for I/O assembly instances
101/151. Elements [2] and [3] of this array can be
selected. Elements [0] and [1] of the array are fixed.
10-13 Warning Parameter
Range:
Function:
0
*
[0 - 65535 ] View a DeviceNet-specific warning word. One
bit is assigned to every warning. Refer to the
VLT
®
DeviceNet Operating Instructions
for further
information.
Bit
Description
0
Bus not active.
1
Explicit connection timeout.
2
I/O connection.
3
Retry limit reached.
4
Actual is not updated.
5
CAN bus off.
Bit
Description
6
I/O send error.
7
Initialisation error.
8
No bus supply.
9
Bus off.
10
Error passive.
11
Error warning.
12
Duplicate MAC ID error.
13
RX queue overrun.
14
TX queue overrun.
15
CAN overrun.
Table 3.16 Warning Bits
10-14 Net Reference
Read only from LCP.
Option: Function:
Select the reference source in instances 21/71 and
20/70.
[0]
*
Off Enables reference via analog/digital inputs.
[1]
On Enables reference via the fieldbus.
10-15 Net Control
Read only from LCP.
Option: Function:
Select the control source in instances 21/71 and 20/70.
[0]
*
Off Enables control via analog/digital inputs.
[1]
On Enable control via the fieldbus.
3.11.4 10-2* COS Filters
10-20 COS Filter 1
Range:
Function:
0
*
[0 -
65535 ]
Enter the value for COS filter 1 to set up the
filter mask for the status word. When operating
in COS (change-of-state), this function filters
out bits in the status word that should not be
sent if they change.
10-21 COS Filter 2
Range:
Function:
0
*
[0 -
65535 ]
Enter the value for COS filter 2, to set up the
filter mask for the Main Actual Value. When
operating in COS (change-of-state), this function
filters out bits in the Main Actual Value that
should not be sent if they change.
Parameter Descriptions
Programming Guide
MG11CE02