2.1.3 Quick Transfer of Parameter Settings
between Multiple Frequency
Converters
Once the set-up of a frequency converter is complete,
store the data in the LCP or on a PC via MCT 10 Set-up
Software Tool.
Auto
on
Reset
Hand
on
Off
Status
Quick
Menu
Main
Menu
Alarm
Log
Back
Canc
el
In
fo
OK
On
Alarm
Warn.
130BA027.10
Illustration 2.18 LCP
Data storage in LCP
NOTICE
Stop the motor before performing this operation.
To store the data in the LCP:
1.
Go to
2.
Press the [OK] key.
3.
Select
[1] All to LCP
.
4.
Press the [OK] key.
All parameter settings are now stored in the LCP indicated
by the progress bar. When 100% is reached, press [OK].
Connect the LCP to another frequency converter and copy
the parameter settings to this frequency converter as well.
Data transfer from LCP to frequency converter
NOTICE
Stop the motor before performing this operation.
To transfer the data from the LCP to the frequency
converter:
1.
Go to
2.
Press the [OK] key.
3.
Select
[2] All from LCP
.
4.
Press the [OK] key.
The parameter settings stored in the LCP are now
transferred to the frequency converter indicated by the
progress bar. When 100% is reached, press [OK].
2.1.4 Parameter Set-Up
The frequency converter can be used for practically all
assignments, thus offering a significant number of
parameters. The series offers a choice between 2
programming modes - the
Quick Menu
mode and the
Main
Menu
mode.
The latter provides access to all parameters. The former
takes the user through a few parameters making it
possible to program the majority of HVAC applications.
Regardless of the programming mode, parameters can be
changed in both
Quick Menu
mode and in
Main Menu
mode.
2.1.5 Quick Menu Mode
Parameter data
The graphical display (GLCP) provides access to all
parameters listed in the
Quick Menu
. The numeric display
(NLCP) only provides access to the
Quick Set-up
parameters.
To set parameters pressing [Quick Menu] - enter or change
parameter data or settings in accordance with the
following procedure:
1.
Press [Quick Menu].
2.
Press [
▲
] or [
▼
] to find the parameter to change.
3.
Press [OK].
4.
Press [
▲
] or [
▼
] to select the correct parameter
setting.
5.
Press [OK].
6.
To move to a different digit within a parameter
setting, use the [
◀
] and [
▶
].
7.
Highlighted area indicates digit selected for
change.
8.
Press [Cancel] to disregard change, or press [OK]
to accept change and enter the new setting.
Example of changing parameter data
Assume
parameter 22-60 Broken Belt Function
is set to
[0]
Off
. To monitor the fan-belt condition, non-broken or
broken, follow this procedure:
1.
Press [Quick Menu].
2.
Press [
▼
] to select
Function Set-ups
.
3.
Press [OK].
4.
Press [
▼
] to select
Application Settings
.
5.
Press [OK].
How to Programme
VLT
®
HVAC Drive FC 102
16
Danfoss A/S © 03/2015 All rights reserved.