3-02 Minimum Reference
Range:
Function:
0.000
Unit
*
[-100000.000 - par.
3-03]
The
Minimum reference
is the minimum value obtained by the
sum of all references.
Minimum reference
is only active if
Min -
Max
[0] is set in par. 3-00.
3-03 Maximum Reference
Range:
Function:
1500.00
0
*
[Par. 3-02 -
100000.000]
Enter the maximum reference. The maximum reference is the
highest value obtainable by adding all references together.
The Maximum Reference unit matches:
•
The choice of configuration in par. 1-00
Configuration
Mode
: for
Speed closed-loop
[1], RPM; for
Torque
[2],
Nm.
•
The unit selected in par. 3-01
Reference/Feedback
Unit
.
3-41 Ramp 1 Ramp-up Time
Range:
Function:
s
*
[0.01 - 3600.00 s]
Enter the ramp-up time, i.e., the acceleration time from 0 RPM
to the rated motor speed n
M,N
(par. 1-25). Choose a ramp-up
time such that the output current does not exceed the current
limit in par. 4-18 during ramping. The value 0.00 corresponds
to 0.01 sec. in speed mode. See ramp-down time in par. 3-42.
Par
. 3
−
41 =
t
acc
s
× n
M, N
(
par
. 1
−
25)
RPM
Δ
ref RPM