[51]
Bahasa Indonesian
Part of Language package 2
1-20 Motor Power
Range:
Function:
Size re-
lated
*
[0.12-1,600 hp
[0.09-1,200 kW]]
Enter the nominal motor power (in kW) according to the motor
nameplate data. The default value corresponds to the nominal
rated output of the unit.
This parameter cannot be adjusted while the motor is running.
This parameter is visible in LCP if par. 0-03 is
International
[0].
1-22 Motor Voltage
Range:
Function:
Size re-
lated
*
[10 - 1,000 V]
Enter the nominal motor voltage according to the motor name-
plate data. The default value corresponds to the nominal rated
output of the unit.
This parameter cannot be adjusted while the motor is running.
1-23 Motor Frequency
Option:
Function:
Min - Max motor frequency: 20 - 1,000 Hz
Select the motor frequency value from the motor nameplate
data. If a value different from 50 Hz or 60 Hz is selected, it is
necessary to adapt the load independent settings in par. 1-50
to 1-53. For 87 Hz operation with 230/400 V motors, set the
nameplate data for 230 V/50 Hz. Adapt par. 4-13
Motor Speed
High Limit [RPM)
and par. 3-03
Maximum Reference
to the 87
Hz application.
[50]
*
50 Hz when parame-
ter 0-03 = interna-
tional
[60]
60 Hz when parame-
ter 0-03 = US
1-24 Motor Current
Range:
Function:
Size re-
lated
*
[0.1 - 10,000 A]
Enter the nominal motor current value from the motor name-
plate data. This data is used for calculating motor torque, motor
thermal protection, etc.
This parameter cannot be adjusted while the motor is running.