380-500 Volt
VLT Type
P250
P315
P355
P400
Max. Input Current [A]
400
472 590 590
647
647
733
684 787
Max. Input Current [A]
460/ 500 436 531 531
580
580
667
667 718
Max. external pre-fuses
1)
[A]
700
900
900
900
Soft Charge Fuses
2)
AC [A]
(qty)
20
(3)
SMPS fuse
3)
[A]
4
AC Fan fuse
3)
[A]
4
15
Supply Voltage [V]
3 Phase, 380-500 ± 10%
Supply Frequency [Hz]
50/
60
Power Factor
greater than 0.90
Efficiency
0.98
Power loss at rated max. load (400 V)
High Overload (150%) [W]
6005
6960
7691
7964
Normal Overload (110%) [W]
7630
7701
8879
9428
Enclosure
IP 00, IP 21/ NEMA 1 & IP 54/ NEMA 12
Vibration Test [g]
0.7
Relative Humidity [%]
93%, +2%, -3% (IEC 68-2-3)
Ambient Temperature
[degrees C]
-10° C to 40° C [14°-104° F] continuously, periodi-
cally at +45° C [113° F]
-25° C to +65°/70° C [-13°-149°/158° F] for stor-
age/ transport
Adjustable Frequency
Drive Protection
Ground and short-circuit protection
Weight
5)
IP 00/ Chassis [kg]
221.4
234.1
236.4
277.3
IP 21/ NEMA 1 [kg]
263.2
270.0
272.3
313.2
IP 54/ NEMA 12 [kg]
263.2
270.0
272.3
313.2
1) Bussman 170M6000 series. See fuse chart.
2) Bussmann FWH-20A6F or exact equivalent, 3 per unit
3) Bussmann KTK-4 or exact equivalent, 1 per unit
4) Littlefuse KLK-15 or exact equivalent, 1 per unit
5) VLT with standard input option, no brake, no load sharing
5. General Specifications
VLT
®
Automation Drive FC 300
Instruction Manual High Power
120
MG.33.U1.22 - VLT
®
is a registered Danfoss trademark.
5