4.1.3. Initial Commissioning
The easiest way of carrying out the initial commissioning is by using the Quick Menu button and
follow the quick set-up procedure using LCP 102 (read table from left to right):
Press
Q2 Quick Menu
0-01 Language
Set language
1-20 Motor power
Set motor nameplate power
1-22 Motor voltage
Set nameplate voltage
1-23 Motor frequency
Set nameplate frequency
1-24 Motor current
Set nameplate current
1-25 Motor nominal speed
Set nameplate speed in RPM
5-12 Terminal 27 Digital
Input
If terminal default is
Coast inverse,
it is
possible to change this setting to
No
function
. No connection to terminal 27
is then needed for running AMA
1-29 Automatic Motor
Adaptation
Set desired AMA function. Enabling
complete AMA is recommended
3-02 Minimum reference
Set the minimum speed of the motor
shaft
3-03 Maximum Reference
Set the maximum speed of the motor
shaft
3-41 Ramp1 up time
Set the ramping-up time with reference
to the nominal motor speed (set in par.
1-25)
3-42 Ramp1 down time
Set the ramping-down time with refer-
ence to the nominal motor speed (set in
par. 1-25)
3-13 Reference site
Set the site from where the reference
must work
VLT
®
Automation Drive FC 300
Instruction Manual High Power