1-20 Motor Power [kW]
Range:
Function:
Size rela-
ted*
[ 0.09 - 3000.00 kW]
Enter the nominal motor power in kW according to the motor nameplate data. The default value
corresponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running. Depending on the choices made in
par. 0-03
Regional Settings
, either par. 1-20
or par. 1-21
made invisible.
1-21 Motor Power [HP]
Range:
Function:
Size rela-
ted*
[ 0.09 - 3000.00 hp]
Enter the nominal motor power in HP according to the motor nameplate data. The default value
corresponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running.
Depending on the choices made in par. 0-03
Regional Settings
, either par. 1-20
is made invisible.
1-22 Motor Voltage
Range:
Function:
Size rela-
ted*
[ 10. - 1000. V]
Enter the nominal motor voltage according to the motor nameplate data. The default value corre-
sponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running.
1-23 Motor Frequency
Range:
Function:
Size rela-
ted*
[20 - 1000 Hz]
Select the motor frequency value from the motor nameplate data.For 87 Hz operation with
230/400 V motors, set the nameplate data for 230 V/50 Hz. Adapt par. 4-13
Maximum Reference
to the 87 Hz application.
NB!
This parameter cannot be adjusted while the motor
is running.
1-24 Motor Current
Range:
Function:
Size rela-
ted*
[ 0.10 - 10000.00 A]
Enter the nominal motor current value from the motor nameplate data. This data is used for cal-
culating motor torque, motor thermal protection etc.
This parameter cannot be adjusted while the motor
is running.
1-25 Motor Nominal Speed
Range:
Function:
Size rela-
ted*
[100 - 60000 RPM]
Enter the nominal motor speed value from the motor nameplate data. This data is used for calcu-
lating automatic motor compensations.
This parameter cannot be adjusted while the motor
is running.
VLT HVAC Drive High Power Operating In-
structions
6 How to Programme
MG.11.F3.02 - VLT
®
is a registered Danfoss trademark
97