6-52 Terminal 42 Output Max Scale
Range:
Function:
100.00 %* [0.00 - 200.00 %]
Scale for the maximum output (20mA) of the analog signal at terminal 42.
Set the value to be the percentage of the full range of the variable selected in par. 6-50
.
130BA075.12
(mA)
0%
20
0/4
100%
Current
Analogue
output
Min Scale
par. 6-93
Variable
for
output
example:
Speed
(RPM)
Analogue
Output
Max Scale
par. 6-94
It is possible to get a value lower than 20mA at full scale by programming values >100% by us-
ing a formula as follows:
20
mA
/
desired
maximum
current
× 100 %
i
.
e
. 10
mA
: 20
mA
10
mA
× 100 % = 200 %
EXAMPLE 1:
Variable value= OUTPUT FREQUENCY, range = 0-100 Hz
Range needed for output = 0-50Hz
Output signal 0 or 4mA is needed at 0Hz (0% of range) - set
par. 6-51
to 0%
Output signal 20mA is needed at 50Hz (50% of range) - set
par. 6-52
0/4 mA
20 mA
50%
100%
0%
50Hz
100Hz
0Hz
130BA858.10
EXAMPLE 2:
Variable= FEEDBACK, range= -200% to +200%
Range needed for output= 0-100%
Output signal 0 or 4mA is needed at 0% (50% of range) - set
par. 6-51
to 50%
Output signal 20mA is needed at 100% (75% of range) - set
par. 6-52
0/4 mA
20 mA
50%
75%
100%
0%
0%
+100%
+200%
-200%
130BA856.10
EXAMPLE 3:
Variable value= REFERENCE, range= Min ref - Max ref
Range needed for output= Min ref (0%) - Max ref (100%), 0-10 mA
Output signal 0 or 4mA is needed at Min ref - set par. 6-51
Output signal 10mA is needed at Max ref (100% of range) - set
par. 6-52
(20mA/10mA x 100%=200%).