6.1.2 Quick Menu Mode
Parameter Data
The graphical display (GLCP) provides access to all parameters listed
under the Quick Menus. The numeric display (NLCP) only provides ac-
cess to the Quick Setup parameters. To set parameters using the
[Quick Menu] button - enter or change parameter data or settings in
accordance with the following procedure:
1.
Press Quick Menu button
2.
Use the [
▲
] and [
▼
] buttons to find the parameter you want
to change
3.
Press [OK]
4.
Use [
▲
] and [
▼
] buttons to select the correct parameter set-
ting
5.
Press [OK]
6.
To move to a different digit within a parameter setting, use
the [
◀
] and [
▶
] buttons
7.
Highlighted area indicates digit selected for change
8.
Press [Cancel] button to disregard change, or press [OK] to
accept change and enter the new setting
Example of changing parameter data
Assume par. 22-60
want to monitor the fan-belt condition - non- broken or broken - ac-
cording to the following procedure
1.
Press Quick Menu key
2.
Choose Function Setups with the [
▼
] button
3.
Press [OK]
4.
Choose Application Settings with the [
▼
] button
5.
Press [OK]
6.
Press [OK] again for Fan Functions
7.
Choose Broken Belt Function by pressing [OK]
8.
With [
▼
] button, choose [2] Trip
The frequency converter will now trip if a broken fan-belt is detected.
Select [My Personal Menu] to display personal parameters:
For example, an AHU or pump OEM may have pre-programmed person-
al parameters to be in My Personal Menu during factory commissioning
to make on-site commissioning/fine tuning simpler. These parameters
are selected in par. 0-25
My Personal Menu
. Up to 20 different parame-
ters can be programmed in this menu.
Select [Changes Made] to get information about:
•
The last 10 changes. Use the up/down navigation keys to
scroll between the last 10 changed parameters.
•
The changes made since default setting.
Select [Loggings]:
to get information about the display line read-outs. The information is
shown as graphs.
Only display parameters selected in par. 0-20
Display Line 1.1 Small
and par. 0-24
Display Line 3 Large
can be viewed. It is possible to store
up to 120 samples in the memory for later reference.
Quick Setup
Efficient Parameter Set-up for VLT HVAC Drive Applications:
The parameters can easily be set up for the vast majority of the VLT
HVAC Drive applications only by using the [Quick Setup] option.
After pressing [Quick Menu], the different choices in the Quick Menu
are listed. See also illustration 6.1 below and tables Q3-1 to Q3-4 in the
following
Function Setups
section.
Example of using the Quick Setup option:
Assume you want to set the Ramp Down Time to 100 seconds:
1.
Select [Quick Setup]. par. 0-01
pears
2.
Press [
▼
] repeatedly until par. 3-42
appears with the default setting of 20 seconds
3.
Press [OK]
4.
Use the [
◀
] button to highlight the 3rd digit before the com-
ma
5.
Change '0' to '1' by using the [
▲
] button
6.
Use the [
▶
] button to highlight the digit '2'
7.
Change '2' to '0' with the [
▼
] button
8.
Press [OK]
The new ramp-down time is now set to 100 sec.
It is recommended to do the set-up in the order listed.
NB!
A complete description of the function is found in the
parameter sections of this manual.
130BP064.10
Q1 My Personal Menu
Q2 Quick Setup
Q3 Function Setups
Q5 Changes Made
40.0% 4.84 A 1(1)
Quick Menus
Illustration 6.1: Quick Menu View
The Quick Setup menu gives access to the 18 most important setup pa-
rameters of the frequency converter. After programming the frequency
converter will, in most cases, be ready for operation. The 18 Quick Set-
up parameters are shown in the table below. A complete description of
the function is given in the parameter description sections of this man-
ual.
6 How to Programme
VLT HVAC Drive High Power Operating In-
structions
94
MG.11.F3.02 - VLT
®
is a registered Danfoss trademark