4.2 Connection Examples
4.2.1 Start/Stop
Terminal 18 = par. 5-10
Terminal 18 Digital Input
[8]
Start
Terminal 27 = par. 5-12
Terminal 27 Digital Input
[0]
No operation
(Default
coast inverse
)
Terminal 37 = Safe stop
12 13 18
37
130BA155.12
32
27
19
29
33 20
P 5-12 [0]
P 5-10 [8]
Start/Stop
+24V
Speed
Safe Stop
Start/Stop
[18]
4.2.2 Pulse Start/Stop
Terminal 18 = par. 5-10
Terminal 18 Digital Input
[9]
Latched start
Terminal 27= par. 5-12
Terminal 27 Digital Input
[6]
Stop inverse
Terminal 37 = Safe stop
12
13
18
37
130BA156.12
32
27
19
29
33
20
P 5 - 12 [6]
P 5 - 10[9]
+24V
Speed
Start
Stop inverse
Safe Stop
Start (18)
Start (27)
4.2.3 Speed Up/Down
Terminals 29/32 = Speed up/down
Terminal 18 = par. 5-10
Terminal 18 Digital Input
Start [9]
(default)
Terminal 27 = par. 5-12
Terminal 27 Digital Input
Freeze ref-
erence [19]
Terminal 29 = par. 5-13
Terminal 29 Digital Input
Speed up
[21]
Terminal 32 = par. 5-14
Terminal 32 Digital Input
Speed down
[22]
NOTE: Terminal 29 only in FC x02 (x=series type).