3.3.7 Installation on the Wall - IP21 (NEMA 1) and IP54 (NEMA 12) Units
This only applies to frame sizes D1 and D2 . It must be considered
where to install the unit.
Take the relevant points into consideration before you select
the final installation site:
•
Free space for cooling
•
Access to open the door
•
Cable entry from the bottom
Mark the mounting holes carefully using the mounting template on the
wall and drill the holes as indicated. Ensure proper distance to the floor
and the ceiling for cooling. A minimum of 225 mm (8.9 inch) below the
frequency converter is needed. Mount the bolts at the bottom and lift
the frequency converter up on the bolts. Tilt the frequency converter
against the wall and mount the upper bolts. Tighten all four bolts to se-
cure the frequency converter against the wall.
176F
A245.10
Illustration 3.33: Lifting method for mounting drive on wall
3.3.8 Gland/Conduit Entry - IP21 (NEMA 1) and IP54 (NEMA12)
Cables are connected through the gland plate from the bottom. Re-
move the plate and plan where to place the entry for the glands or con-
duits. Prepare holes in the marked area on the drawing.
NB!
The gland plate must be fitted to the frequency
converter to ensure the specified protection degree,
as well as ensuring proper cooling of the unit. If the
gland plate is not mounted, the frequency converter
may trip on Alarm 69, Pwr. Card Temp
Cable entries viewed from the bottom of the frequency
converter - 1) Mains side 2) Motor side
130BB073.10
Illustration 3.34: Example of Proper Installation of Gland
Plate.
2
1
176F
A289.11
98.6
62.5
130.0
35
202.8
350
Illustration 3.35: Frame Sizes D1 + D2
VLT HVAC Drive High Power Operating In-
structions
3 Mechanical Installation
MG.11.F3.02 - VLT
®