Max. input current
130BA229.10
Continuous
(at 550 V ) [A]
743
866
962
1079
1282
1440
Continuous
(at 575 V) [A]
711
828
920
1032
1227
1378
Continuous
(at 690 V) [A]
711
828
920
1032
1227
1378
Max. cable size,motor [mm
2
(AWG
2)
)]
8x150
(8x300 mcm)
12x150
(12x300 mcm)
Max. cable size,mains F1/F2
[mm
2
(AWG
2)
)]
8x240
(8x500 mcm)
Max. cable size,mains F3/F4
[mm
2
(AWG
2)
)]
8x456
8x900 mcm
Max. cable size, loadsharing
[mm
2
(AWG
2)
)]
4x120
(4x250 mcm)
Max. cable size, brake [mm
2
(AWG
2)
)
4x185
(4x350 mcm)
6x185
(6x350 mcm)
Max. external pre-fuses [A]
1)
1600
2000
2500
Est. power loss
at rated max. load [W]
4)
, 600 V,
F1 & F2
10771
12272
13835
15592
18281
20825
Est. power loss
at rated max. load [W]
4)
, 690 V,
F1 & F2
11315
12903
14533
16375
19207
21857
Max added losses of Circuit
Breaker or Disconnect & Contac-
tor, F3 & F4
427
532
615
665
863
1044
Max Panel Options Losses
400
Weight,enclosure IP21, IP 54
[kg]
1004/ 1299
1004/ 1299
1004/ 1299
1246/ 1541
1246/ 1541
1280/1575
Weight, Rectifier
Module [kg]
102
102
102
136
136
136
Weight, Inverter
Module [kg]
102
102
136
102
102
136
Efficiency
4)
0.98
Output frequency
0-500 Hz
Heatsink overtemp. trip
95
°
C
Power card amb. trip
68
°
C
1) For type of fuse see section
Fuses.
2) American Wire Gauge.
3) Measured using 5 m screened motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be /-15% (tolerence relates to variety in voltage and cable
conditions). Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the power loss
in the frequency converter and opposite. If the switching frequency is increased comed to the default setting, the power losses may rise sig-
nificantly.LCP and typical control card power consumptions are included. Further options and customer load may add up to 30W to the losses.
(Though typical only 4W extra for a fully loaded control card, or options for slot A or slot B, each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/-5%).
VLT HVAC Drive High Power Operating In-
structions
7 General Specifications
MG.11.F3.02 - VLT
®
is a registered Danfoss trademark
175
7