4.1.15 Mains Disconnectors - Frame Size D, E and F
Frame
size
Power & Voltage
Type
D1/D3
P110-P132 380-480V &
P110-P160 525-690V
ABB OETL-NF200A or
OT200U12-91
D2/D4
P160-P250 380-480V &
P200-P400 525-690V
ABB OETL-NF400A or
OT400U12-91
E1/E2
P315 380-480V & P450-
P630 525-690V
ABB OETL-NF600A
E1/E2
P355-P450 380-480V
ABB OETL-NF800A
F3
P500 380-480V & P710-
P800 525-690V
Merlin Gerin
NPJF36000S12AAYP
F3
P560-P710 380-480V &
P900 525-690V
Merlin Gerin
NRK36000S20AAYP
F4
P800-P1M0 380-480V &
P1M0-P1M4 525-690V
Merlin Gerin
NRK36000S20AAYP
4.1.16 F Frame circuit breakers
Fram
e size
Power & Voltage
Type
F3
P500 380-480V & P710-
P800 525-690V
Merlin Gerin
NPJF36120U31AABSCYP
F3
P560-P710 380-480V &
P900 525-690V
Merlin Gerin
NRJF36200U31AABSCYP
F4
P800 380-480V & P1M0-
P1M4 525-690V
Merlin Gerin
NRJF36200U31AABSCYP
F4
P1M0 380-480V
Merlin Gerin
NRJF36250U31AABSCYP
4.1.17 F Frame Mains Contactors
Frame
size
Power & Voltage
Type
F3
P500-P560 380-480V &
P710-P900 525-690V
Eaton XTCE650N22A
F3
P 630-P710380-480V
Eaton XTCEC14P22B
F4
P800-P1M0 380-480V &
P1M0-P1M4 525-690V
Eaton XTCEC14P22B
4.1.18 Motor Insulation
For motor cable lengths
≤
the maximum cable length listed in the Gen-
eral Specifications tables the following motor insulation ratings are rec-
ommended because the peak voltage can be up to twice the DC link
voltage, 2.8 times the mains voltage, due to transmission line effects in
the motor cable. If a motor has lower insulation rating it recommended
to use a du/dt or sine wave filter.
Nominal Mains Voltage
Motor Insulation
U
N
≤
420 V
Standard U
LL
= 1300V
420V < U
N
≤ 500 V
Reinforced U
LL
= 1600V
500V < U
N
≤ 600 V
Reinforced U
LL
= 1800V
600V < U
N
≤ 690 V
Reinforced U
LL
= 2000V
4 Electrical Installation
VLT HVAC Drive High Power Operating In-
structions
70
MG.11.F3.02 - VLT
®
is a registered Danfoss trademark
4