Bit Bit = 0
Bit = 1
00 Preset reference option lsb
–
01 Preset reference option 2
nd
bit of
preset references
–
02 DC brake
Ramp
03 Coasting
Enable
04 Quick stop
Ramp
05 Freeze output
Ramp
06 Ramp stop
Start
07 No function
Reset
08 No function
Jog
09 Ramp 1
Ramp 2
10 Data not valid
Valid
11 Relay_A not active
Relay_A activated
12 Relay_B not active
Relay_B activated
13 Choice of set-up lsb
–
14 No function
No function
15 No function
Reversing
Table 3.5 Control Word
16-01 Reference [Unit]
Range:
Function:
0 Referen-
ceFeedback
Unit
*
[-4999 - 4999
Reference-
FeedbackUnit]
View the present reference value
applied on impulse or analog basis
in the unit resulting from the
configuration selected in
parameter 1-00 Configuration Mode
16-02 Reference [%]
Range:
Function:
0 %
*
[-200 -
200 %]
View the total reference. The total
reference is the sum of digital,
analog, preset, bus, and freeze
references.
16-03 Status Word
Range:
Function:
0
*
[0 - 65535 ]
View the status word sent from the
frequency converter via the serial
communication port in hex code.
Bit Bit=0
Bit=1
00 Control not ready
Ready
01 VLT not ready
Ready
02 Coasting
Enable
03 No fault
Trip
04 No warning
Warning
05 Reserved
–
06 No trip lock
Trip lock
07 No warning
Warning
08 Speed
≠
ref.
Speed=ref.
09 Local control
Bus control
10 Out of range
Frequency OK
11 Not running
Running
12 No function
No function
13 Voltage OK
Above limit
14 Current OK
Above limit
15 Temperature OK
Above limit
Table 3.6 Status Word
16-05 Main Actual Value [%]
Range:
Function:
0 %
*
[-200 -
200 %]
View the 2 byte word sent with the
status word to the bus master
reporting the main actual value.
16-09 Custom Readout
Range:
Function:
0 Custom-
ReadoutUni
t
*
[0 - 9999
CustomRea-
doutUnit]
View the user-defined readouts as
defined in
,
parameter 0-31 Custom Readout Min
Value
, and
.
3.12.2 16-1* Motor Status
16-10 Power [kW]
Range:
Function:
0 kW
*
[0 - 1000
kW]
Shows the actual compressor power
in kW. The value shown is
calculated based on the actual
compressor voltage and compressor
current.
16-11 Power [hp]
Range:
Function:
0 hp
*
[0 - 1000 hp] View the actual compressor power
in hp. The value shown is
calculated based on the actual
compressor voltage and compressor
current.
Parameters
Programming Guide
MG18P202
Danfoss A/S © 06/2019 All rights reserved.
59