4 Troubleshooting
4.1 Alarms and Warnings
A warning or an alarm is signaled by the relevant LED on
the front of the frequency converter and indicated by a
code on the display.
A warning remains active until its cause is no longer
present. Under certain circumstances, operation of the
compressor may still be continued. Warning messages may
be critical.
In the event of an alarm, the frequency converter has
tripped. To restart operation, reset alarms once their cause
has been rectified.
This may be done in 4 ways:
•
By pressing [Reset].
•
Via a digital input with the
Reset
function.
•
Via serial communication.
•
By resetting automatically using the [Auto Reset]
function, see
parameter 14-20 Reset Mode
.
NOTICE
After a manual reset pressing [Reset], press [Auto On] or
[Hand On] to restart the compressor.
If an alarm cannot be reset, the reason may be that its
cause has not been rectified, or the alarm is trip-locked,
see
CAUTION
Alarms that are trip-locked offer extra protection,
meaning that the mains supply must be switched off
before the alarm can be reset. After being switched back
on, the frequency converter is no longer blocked and
may be reset as described above once the cause has
been rectified.
Alarms that are not trip-locked can also be reset using
the automatic reset function in
parameter 14-20 Reset
Mode
(Warning: automatic wake-up is possible!)
specifies whether a warning occurs before an
alarm, or whether to show a warning or an alarm for a
given fault.
This is possible, for instance, in
parameter 1-90 Motor
Thermal Protection
. After an alarm or trip, the compressor
carries on coasting, and the alarm and warning flash on
the frequency converter. Once the problem has been
rectified, only the alarm continues flashing.
Fault
number
Alarm/
Warning bit
number
Fault text
Warning
Alarm
Trip
locked
Cause of problem
2
16
Live zero error
X
X
Signal on terminal 53 or 54 is less than 50% of the value set
in
parameter 6-10 Terminal 53 Low Voltage
parameter 6-12 Terminal 53 Low Current
,
parameter 6-20 Terminal 54 Low Voltage
, or
parameter 6-22 Terminal 54 Low Current
. See also parameter
group
6-0* Analog I/O Mode
.
4
14
Mains ph. loss
X
X
X
Missing phase on the supply side or too high voltage
imbalance. Check the supply voltage. See
parameter 14-12 Response to Mains Imbalance
7
11
DC over volt
X
X
DC-link voltage exceeds limit.
8
10
DC under volt
X
X
DC-link voltage drops below
voltage warning low
limit.
9
9
Inverter overload
X
X
More than 100% load for too long.
10
8
Motor ETR
overtemperature
X
X
The motor is too hot due to more than 100% load for too
long. See
parameter 1-90 Motor Thermal Protection
11
7
Motor thermistor
overtemperature
X
X
The thermistor or the thermistor connection is disconnected.
See
parameter 1-90 Motor Thermal Protection
13
5
Overcurrent
X
X
X
Inverter peak current limit is exceeded.
14
2
Earth Fault
X
X
X
Discharge from output phases to ground.
16
12
Short Circuit
X
X
Short circuit in the compressor or on the compressor
terminals.
17
4
Ctrl. word TO
X
X
No communication to the frequency converter. See parameter
group
8-0* General Settings
.
Troubleshooting
VLT
®
Compressor Drive CDS 803
66
Danfoss A/S © 06/2019 All rights reserved.
MG18P202
4
4