1.
Press [Menu] until indicator in display is placed
above
Main Menu
.
2.
Press [
▲
] [
▼
] to browse through the parameter
groups.
3.
Press [OK] to select a parameter group.
4.
Press [
▲
] [
▼
] to browse through the parameters in
the specific group.
5.
Press [OK] to select the parameter.
6.
Press [
▲
] [
▼
] to set/change the parameter value.
Press [Back] to go back one level.
2.4 Quick Transfer of Parameter Settings
between Multiple Frequency Converters
Once the set-up of a frequency converter is complete,
Danfoss recommends storing the data in the LCP or on a
PC via MCT 10 Set-up Software tool.
Data transfer from frequency converter to LCP:
WARNING
Stop the compressor before performing this operation.
1.
Go to
2.
Press [OK].
3.
Select
[1] All to LCP
.
4.
Press [OK].
Connect the LCP to another frequency converter and copy
the parameter settings to this frequency converter as well.
Data transfer from LCP to frequency converter:
WARNING
Stop the compressor before performing this operation.
1.
Go to
2.
Press [OK].
3.
Select
[2] All from LCP
.
4.
Press [OK].
2.5 Readout and Programming of Indexed
Parameters
Select the parameter, press [OK], and press [
▲
]/[
▼
] to scroll
through the indexed values. To change the parameter
value, select the indexed value and press [OK]. Change the
value by pressing [
▲
]/[
▼
]. Press [OK] to accept the new
setting. Press [Cancel] to abort. Press [Back] to leave the
parameter.
2.6 Initialize the Frequency Converter to
Default Settings in 2 Ways
Recommended initialization (via
parameter 14-22 Operation Mode
1.
Select
parameter 14-22 Operation Mode
.
2.
Press [OK].
3.
Select
[2] Initialisation
and Press [OK].
4.
Cut off the mains supply and wait until the
display turns off.
5.
Reconnect the mains supply - the frequency
converter is now reset.
Except the following parameters:
•
Parameter 1-06 Clockwise Direction
•
•
•
•
Parameter 8-33 Parity / Stop Bits
•
Parameter 8-35 Minimum Response Delay
•
Parameter 8-36 Maximum Response Delay
•
Parameter 8-37 Maximum Inter-char delay
•
Parameter 15-00 Operating hours
to
parameter 15-05 Over Volt's
•
•
•
•
Parameter 15-30 Alarm Log: Error Code
•
Parameter group 15-4* Drive identification
parameters
2-finger initialization
1.
Power off the frequency converter.
2.
Press [OK] and [Menu].
3.
Power up the frequency converter while still
pressing the keys above for 10 s.
4.
The frequency converter is now reset, except the
following parameters:
•
Parameter 15-00 Operating hours
•
•
•
•
Parameter group 15-4* Drive identification
parameters
Initialization of parameters is confirmed by AL80 in the
display after the power cycle.
How to Program
Programming Guide
MG18P202