13-01 Start Event
To activate smart logic controller, select the boolean (TRUE or
FALSE) input.
Option:
Function:
[0]
False
Enters the fixed value of FALSE in
the logic rule.
[1]
True
Enters the fixed value TRUE in the
logic rule.
[2]
Running
The compressor runs.
[3]
In range
The compressor runs within the
programmed current ranges
(
parameter 4-50 Warning Current
and
[4]
On reference
The compressor runs at reference
speed.
[7]
Out of current
range
The compressor current is outside
the range set in
.
[8]
Below I low
The compressor current is lower
than set in
.
[9]
Above I high
The compressor current is higher
than set in
[16]
Thermal
warning
The thermal warning turns on when
the temperature exceeds the limit
in the compressor, the frequency
converter, or the thermistor.
[17]
Mains out of
range
[18]
Reversing
The frequency converter reverses.
[19]
Warning
A warning is present.
[20]
Alarm (trip)
An alarm is present.
[21]
Alarm (trip
lock)
A trip lock alarm is present.
[22]
Comparator 0
Use the result of comparator 0 in
the logic rule.
[23]
Comparator 1
Use the result of comparator 1 in
the logic rule.
[24]
Comparator 2
Use the result of comparator 2 in
the logic rule.
[25]
Comparator 3
Use the result of comparator 3 in
the logic rule.
[26]
Logic rule 0
Use the result of logic rule 0 in the
logic rule.
[27]
Logic rule 1
Use the result of logic rule 1 in the
logic rule.
13-01 Start Event
To activate smart logic controller, select the boolean (TRUE or
FALSE) input.
Option:
Function:
[28]
Logic rule 2
Use the result of logic rule 2 in the
logic rule.
[29]
Logic rule 3
Use the result of logic rule 3 in the
logic rule.
[33]
Digital input
DI18
Use the value of DI18 in the logic
rule (High = TRUE).
[34]
Digital input
DI19
Use the value of DI19 in the logic
rule (High = TRUE).
[35]
Digital input
DI27
Use the value of DI27 in the logic
rule (High = TRUE).
[36]
Digital input
DI29
Use the value of DI29 in the logic
rule (High = TRUE).
[39]
*
Start
command
This event is TRUE if the frequency
converter is started (either via
digital input, fieldbus, or other).
[40]
Drive stopped This event is TRUE if the frequency
converter is stopped or coasted
(either via digital input, fieldbus, or
other).
[42]
Auto Reset
Trip
This event is TRUE if the frequency
converter is tripped (but not trip
lock) and an automatic reset is
issued.
[50]
Comparator 4
Use the result of comparator 4 in
the logic rule.
[51]
Comparator 5
Use the result of comparator 5 in
the logic rule.
[60]
Logic rule 4
Use the result of logic rule 4 in the
logic rule.
[61]
Logic rule 5
Use the result of logic rule 5 in the
logic rule.
13-02 Stop Event
Select the condition (TRUE or FALSE) which deactivates the smart
logic controller.
Option:
Function:
[0]
False
Enters the fixed value of FALSE in
the logic rule.
[1]
True
Enters the fixed value TRUE in the
logic rule.
[2]
Running
See
parameter 13-01 Start Event
for
further description.
[3]
In range
See
parameter 13-01 Start Event
for
further description.
[4]
On reference
See
parameter 13-01 Start Event
for
further description.
Parameters
VLT
®
Compressor Drive CDS 803
46