Parameter
Option
Default
Function
Parameter 3-42 Ramp 1 Ramp Down
Time
0.05–3600.0 s
30.00 s
Ramp-down time from nominal motor speed
to 0.
Parameter 5-12 Terminal 27 Digital
Input
[0] No operation
[1] Reset
[2] Coast inverse
[3] Coast and reset inverse
[4] Quick stop inverse
[5] DC-brake inverse
[6] Stop inverse
[7] External Interlock
[8] Start
[9] Latched start
[10] Reversing
[11] Start reversing
[14] Jog
[16] Preset ref bit 0
[17] Preset ref bit 1
[18] Preset ref bit 2
[19] Freeze reference
[20] Speed up
[22] Speed down
[23] Set-up select bit 0
[34] Ramp bit 0
[52] Run permissive
[53] Hand start
[54] Auto start
[60] Counter A (up)
[61] Counter A (down)
[62] Reset Counter A
[63] Counter B (up)
[64] Counter B (down)
[65] Reset Counter B
[6] Stop inverse
Select the input function for terminal 27.
[0]
Function relay
See
Alarm
Select the function to control output relay 1.
[1]
Function relay
See
Drive running
Select the function to control output relay 2.
Parameter 6-10 Terminal 53 Low
Voltage
0–10 V
0.07 V
Enter the voltage that corresponds to the low
reference value.
Parameter 6-11 Terminal 53 High
Voltage
0–10 V
10 V
Enter the voltage that corresponds to the high
reference value.
Parameter 6-14 Terminal 53 Low Ref./
Feedb. Value
-4999 – 4999
Size related
Enter the reference value that corresponds to
the voltage set in
parameter 6-10 Terminal 53
Low Voltage
.
Parameter 6-15 Terminal 53 High Ref./
Feedb. Value
-4999 – 4999
200
Enter the reference value that corresponds to
the voltage set in
parameter 6-11 Terminal 53
High Voltage
.
Parameter 6-22 Terminal 54 Low
Current
0.00–20.00 mA
4.00 mA
Enter the current that corresponds to the low
reference value.
Parameter 6-23 Terminal 54 High
Current
0–10 V
10 V
Enter the current that corresponds to the high
reference value.
Parameter 6-24 Terminal 54 Low Ref./
Feedb. Value
-0.00–20.00 mA
20.00 mA
Enter the reference value that corresponds to
the current set in
How to Program
Programming Guide
MG18P202