6-20 Terminal 54 Low Voltage
Range:
Function:
parameter 6-01 Live Zero Timeout
Function
, set the value to >1 V.
6-21 Terminal 54 High Voltage
Range:
Function:
10 V
*
[0 - 10 V]
Enter the voltage (V) that
corresponds to the high reference
value (set in
parameter 6-25 Terminal 54 High
Ref./Feedb. Value
6-22 Terminal 54 Low Current
Range:
Function:
4 mA
*
[0 - 20 mA]
Enter the low current value. This
reference signal corresponds to the
low reference/ feedback value set in
parameter 6-24 Terminal 54 Low Ref./
Feedb. Value
. To activate the live
zero timeout function in
parameter 6-01 Live Zero Timeout
Function
, set the value to >2 mA.
6-23 Terminal 54 High Current
Range:
Function:
20 mA
*
[0 - 20 mA]
Enter the high current value
corresponding to the high
reference/feedback value set in
parameter 6-25 Terminal 54 High
Ref./Feedb. Value
6-24 Terminal 54 Low Ref./Feedb. Value
Range:
Function:
0
*
[-4999 -
4999 ]
Enter the reference or feedback
value that corresponds to the
voltage or current set in
parameter 6-21 Terminal 54 High
Voltage
/
.
6-25 Terminal 54 High Ref./Feedb. Value
Range:
Function:
Size
related
*
[-4999 -
4999 ]
Enter the reference or feedback
value that corresponds to the
voltage or current set in
parameter 6-21 Terminal 54 High
Voltage
/
6-26 Terminal 54 Filter Time Constant
Range:
Function:
0.01 s
*
[0.01 - 10 s]
Enter the time constant, which is a
firstorder digital low-pass filter time
6-26 Terminal 54 Filter Time Constant
Range:
Function:
constant for suppressing electrical
noise in terminal 54. A high time
constant value improves
dampening, but also increases the
time delay through the filter.
6-29 Terminal 54 mode
Select if terminal 54 is used for current- or voltage input.
Option:
Function:
[0]
*
Current mode
[1]
Voltage mode
3.7.4 6-7* Analog/Digital Output 45
Parameters for configuring the scaling and limits for
analog/digital output terminal 45. Analog outputs are
current outputs: 0/4–20 mA. Resolution on analog output
is 12 bit. Analog output terminals can also be set up as
digital output.
6-70 Terminal 45 Mode
Set terminal 45 to act as analog output or as digital output.
Option:
Function:
[0]
*
0-20 mA
[1]
4-20 mA
[2]
Digital Output
6-71 Terminal 45 Analog Output
Select the function of terminal 45 as an analog current output.
See also
parameter 6-70 Terminal 45 Mode
.
Option:
Function:
[0]
*
No operation
[100]
Output
frequency
0–400 Hz
[101]
Reference
Min
Ref.
–Max
Ref.
[102]
Feedback
Min
FB
–Max
FB
[103]
Motor Current 0–I
max
[106]
Power
0–P
nom
[139]
Bus Control
0–100%
[254]
DC Link
Voltage
6-72 Terminal 45 Digital Output
Select the function of terminal 45 as a digital current output. See
also
parameter 6-70 Terminal 45 Mode
. See
for description of the options.
Option:
Function:
[0]
*
No operation
[1]
Control Ready
[2]
Drive ready
Parameters
Programming Guide
MG18P202