13-40 Logic Rule Boolean 1
Array [6]
Select the first boolean (TRUE or FALSE) input for the selected
logic rule.
Option:
Function:
[34]
Digital input
DI19
Use the value of DI19 in the logic
rule (High=TRUE).
[35]
Digital input
DI27
Use the value of DI27 in the logic
rule (High=TRUE).
[36]
Digital input
DI29
Use the value of DI29 in the logic
rule (High=TRUE).
[39]
Start
command
This logic rule is TRUE if the
frequency converter is started by
any means (either via digital input,
or other).
[40]
Drive stopped This logic rule is TRUE if the
frequency converter is stopped or
coasted by any means (either via
digital input, or other).
[42]
Auto Reset
Trip
This logic rule is TRUE if the
frequency converter is tripped (but
not trip lock) and an automatic
reset is issued.
[50]
Comparator 4
Use the result of comparator 4 in
the logic rule.
[51]
Comparator 5
Use the result of comparator 5 in
the logic rule.
[60]
Logic rule 4
Use the result of logic rule 4 in the
logic rule.
[61]
Logic rule 5
Use the result of logic rule 5 in the
logic rule.
[70]
SL Time-out 3 Use the result of timer 3 in the
logic rule.
[71]
SL Time-out 4 Use the result of timer 4 in the
logic rule.
[72]
SL Time-out 5 Use the result of timer 5 in the
logic rule.
[73]
SL Time-out 6 Use the result of timer 6 in the
logic rule.
[74]
SL Time-out 7 Use the result of timer 7 in the
logic rule.
13-41 Logic Rule Operator 1
Select the first logical operator to use on the Boolean inputs
from
parameter
and
parameter
.
Option:
Function:
[0]
*
Disabled
[1]
AND
[2]
OR
[3]
AND NOT
13-41 Logic Rule Operator 1
Select the first logical operator to use on the Boolean inputs
from
parameter
and
parameter
.
Option:
Function:
[4]
OR NOT
[5]
NOT AND
[6]
NOT OR
[7]
NOT AND NOT
[8]
NOT OR NOT
13-42 Logic Rule Boolean 2
Array [6]
Select the second boolean (TRUE or FALSE) input for the selected
logic rule.
See
parameter 13-40 Logic Rule Boolean 1
for further descriptions
of options and their functions.
Option:
Function:
[0]
*
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[7]
Out of current
range
[8]
Below I low
[9]
Above I high
[16]
Thermal
warning
[17]
Mains out of
range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip
lock)
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[30]
SL Time-out 0
[31]
SL Time-out 1
[32]
SL Time-out 2
[33]
Digital input
DI18
[34]
Digital input
DI19
[35]
Digital input
DI27
[36]
Digital input
DI29
Parameters
VLT
®
Compressor Drive CDS 803
50