13-20 SL Controller Timer
Range:
Function:
74] Start timer X) and until the
timer value has elapsed. Array
parameters contain timers 0–7.
3.9.5 13-4* Logic Rules
Combine up to 3 boolean inputs (true/false inputs) from
timers, comparators, digital inputs, status bits, and events
using the logical operators AND, OR, and NOT. Select
boolean inputs for the calculation in
parameter 13-42 Logic Rule Boolean 2
, and
parameter 13-44 Logic Rule Boolean 3
. Define the operators
used to combine the selected inputs logically in
parameter 13-41 Logic Rule Operator 1
and
parameter 13-43 Logic Rule Operator 2
. . .
. . .
. . .
. . .
Par. 13-43
Logic Rule Operator 2
Par. 13-41
Logic Rule Operator 1
Par. 13-40
Logic Rule Boolean 1
Par. 13-42
Logic Rule Boolean 2
Par. 13-44
Logic Rule Boolean 3
130BB673.10
Illustration 3.13 Logic Rules
Priority of calculation
The results of
parameter 13-40 Logic Rule Boolean 1
parameter 13-41 Logic Rule Operator 1
, and
parameter 13-42 Logic Rule Boolean 2
are calculated first.
The outcome (true/false) of this calculation is combined
with the settings of
parameter 13-43 Logic Rule Operator 2
and
parameter 13-44 Logic Rule Boolean 3
, yielding the final
result (true/false) of the logic rule.
13-40 Logic Rule Boolean 1
Array [6]
Select the first boolean (TRUE or FALSE) input for the selected
logic rule.
Option:
Function:
[0]
*
False
Enters the fixed value of FALSE in
the logic rule.
[1]
True
Enters the fixed value TRUE in the
logic rule.
[2]
Running
See
for
further description.
[3]
In range
See
for
further description.
[4]
On reference
See
for
further description.
13-40 Logic Rule Boolean 1
Array [6]
Select the first boolean (TRUE or FALSE) input for the selected
logic rule.
Option:
Function:
[7]
Out of current
range
See
for
further description.
[8]
Below I low
See
for
further description.
[9]
Above I high
See
for
further description.
[16]
Thermal
warning
See
for
further description.
[17]
Mains out of
range
See
for
further description.
[18]
Reversing
See
for
further description.
[19]
Warning
See
for
further description.
[20]
Alarm (trip)
See
for
further description.
[21]
Alarm (trip
lock)
See
for
further description.
[22]
Comparator 0
Use the result of comparator 0 in
the logic rule.
[23]
Comparator 1
Use the result of comparator 1 in
the logic rule.
[24]
Comparator 2
Use the result of comparator 2 in
the logic rule.
[25]
Comparator 3
Use the result of comparator 3 in
the logic rule.
[26]
Logic rule 0
Use the result of logic rule 0 in the
logic rule.
[27]
Logic rule 1
Use the result of logic rule 1 in the
logic rule.
[28]
Logic rule 2
Use the result of logic rule 2 in the
logic rule.
[29]
Logic rule 3
Use the result of logic rule 3 in the
logic rule.
[30]
SL Time-out 0 Use the result of timer 0 in the
logic rule.
[31]
SL Time-out 1 Use the result of timer 1 in the
logic rule.
[32]
SL Time-out 2 Use the result of timer 2 in the
logic rule.
[33]
Digital input
DI18
Use the value of DI18 in the logic
rule (High=TRUE).
Parameters