0-31 Custom Readout Min Value
This parameter sets the minimum value of the customdefined
readout (occurs at 0 speed). It is only possible to select a value
different from 0 when selecting a linear unit in
parameter 0-30 Custom Readout Unit
. For quadratic and cubic
units, the minimum value is 0.
Range:
Function:
0 Custom-
ReadoutUni
t
*
[ 0 -
999999.99
CustomRea-
doutUnit]
0-32 Custom Readout Max Value
This parameter sets the maximum value to be shown when the
speed of the compressor has reached the set value for
parameter 4-14 Motor Speed High Limit [Hz]
Range:
Function:
100
Custom-
ReadoutUni
t
*
[ 0.0 -
999999.99
CustomRea-
doutUnit]
3.1.3 0-4* LCP Keypad
Enable and disable individual keys on the LCP keypad.
0-40 [Hand on] Key on LCP
Option:
Function:
[0]
Disabled
To avoid unintended start of the
frequency converter in
hand-on
mode
, select
[0] Disabled
.
[1]
*
Enabled
[Hand On] is enabled.
0-42 [Auto on] Key on LCP
Option:
Function:
[0]
Disabled
To avoid unintended start of the
frequency converter from the LCP,
select
[0] Disabled
.
[1]
*
Enabled
[Auto On] is enabled.
0-44 [Off/Reset] Key on LCP
Option:
Function:
[0]
Disabled
Disable the off/reset key.
[1]
*
Enabled
Enable both off and reset functions.
[7]
Enable Reset
Only
Enable the reset function, and
disable the off function to avoid
unintended stop of the frequency
converter.
3.1.4 0-5* Copy/Save
0-50 LCP Copy
Option:
Function:
[0]
*
No copy
[1]
All to LCP
Copies all parameters in all set-ups
from the frequency converter
memory to the LCP memory. For
service purposes, to copy all
parameters to the LCP after
commissioning.
[2]
All from LCP
Copies all parameters in all set-ups
from the LCP memory to the
frequency converter memory.
[3]
Size indep.
from LCP
Copies only the parameters that are
independent of the compressor
size. The latter selection can be
used to program several frequency
converters with the same function
without disturbing compressor data
which are already set.
0-51 Set-up Copy
Option:
Function:
[0]
*
No copy
No function.
[1]
Copy from
setup 1
Copy from set-up 1 to set-up 2.
[2]
Copy from
setup 2
Copy from set-up 2 to set-up 1.
[9]
Copy from
Factory setup
Copy factory setting to
programming setup (selected in
parameter 0-11 Programming Set-
up
).
3.1.5 0-6* Password
0-60 Main Menu Password
Define the password for access to the Main Menu via the [Main
Menu] key. Setting the value to 0 disables the password function.
Range:
Function:
0
*
[0 - 999 ]
3.2 Main Menu - Load and Motor - Group 1
Parameters related to the compressor nameplate load
compensations and application load type.
Parameters
Programming Guide
MG18P202
Danfoss A/S © 06/2019 All rights reserved.
21