16-72 Counter A
Range:
Function:
0
*
[-2147483648
- 2147483647 ]
View the present value of Counter A.
Counters are useful as comparator
operands, see
The value can be reset or changed either
via digital inputs (parameter group
5-1*
Digital Inputs
) or by using an SLC action
(
parameter 13-52 SL Controller Action
16-73 Counter B
Range:
Function:
0
*
[-2147483648
- 2147483647 ]
View the present value of Counter B.
Counters are useful as comparator operands
(
parameter 13-10 Comparator Operand
).
The value can be reset or changed either
via digital inputs (parameter group 5-1*
Digital Inputs) or by using an SLC action
(
parameter 13-52 SL Controller Action
).
16-74 Prec. Stop Counter
Range:
Function:
0
*
[0 - 2147483647 ] Returns the actual counter value of
precise counter (
parameter 1-84 Precise
Stop Counter Value
).
6.13.5 16-8* Fieldbus & FC Port
Parameters for reporting the BUS references and control
words.
16-80 Fieldbus CTW 1
Range:
Function:
0
*
[0 -
65535 ]
View the two-byte control word (CTW) received
from the Bus-Master. Interpretation of the
control word depends on the fieldbus option
installed and the control word profile selected in
parameter 8-10 Control Profile
.
For more information, refer to the relevant
fieldbus manual.
16-82 Fieldbus REF 1
Range:
Function:
0
*
[-200 - 200 ] View the two-byte word sent with the control
word from the Bus-Master to set the
reference value.
For more information, refer to the relevant
fieldbus manual.
16-84 Comm. Option Status
Range:
Function:
0
*
[0 - 65535 ] View the extended fieldbus comm. option
status word.
For more information, refer to the relevant
fieldbus manual.
16-86 FC Port REF 1
Range:
Function:
0
*
[-200 -
200 ]
View the two-byte status word (STW) sent to
the Bus-Master. Interpretation of the status word
depends on the fieldbus option installed and
the control word profile selected in
parameter 8-10 Control Profile
.
16-86 FC Port REF 1
Range:
Function:
0
*
[-200 -
200 ]
View the two-byte status word (STW) sent to
the bus master. Interpretation of the status word
depends on the serial communication bus
option installed and the control word profile
selected in
parameter 8-10 Control Profile
.
6.13.6 16-9* Diagnosis Read-Outs
NOTICE!
When using MCT 10 Set-up Software, the readout
parameters can only be read online, i.e. as the actual
status. This means that the status is not stored in the
MCT 10 Set-up Software file.
16-90 Alarm Word
Range:
Function:
0
*
[0 - 4294967295 ] View the alarm word sent via the serial
communication port in hex code.
16-91 Alarm Word 2
Range:
Function:
0
*
[0 - 4294967295 ] View the alarm word sent via the serial
communication port in hex code.
16-92 Warning Word
Range:
Function:
0
*
[0 - 4294967295 ] View the warning word sent via the
serial communication port in hex code.
16-93 Warning Word 2
Range:
Function:
0
*
[0 - 4294967295 ] View the warning word sent via the
serial communication port in hex code.
Parameter Descriptions
VLT
®
Compressor Drives CDS 302/CDS 303
110
Danfoss A/S © Rev. 2013-07-03 All rights reserved.
MG34M422
6
6
Summary of Contents for VLT CDS 303
Page 2: ......