Enclosure
Size
Power [kW]
Recommended
fuse size
Recommended
Max. fuse
Recommended circuit
breaker
Max trip level [A]
Moeller
B1
11-18
gG-25 (11)
gG-32 (15)
gG-40 (18.5)
gG-80
PKZM4-63
63
B2
22-30
gG-50 (22)
gG-63 (30)
gG-100
NZMB1-A100
100
B3
11-15
gG-25 (11)
gG-32 (15)
gG-63
PKZM4-50
50
B4
18.5-30
gG-40 (18.5)
gG-50 (22)
gG-63 (30)
gG-125
NZMB1-A100
100
C1
37-55
gG-63 (37)
gG-100 (45)
aR-160 (55)
gG-160 (37-45)
aR-250 (55)
NZMB2-A200
160
C2
75
aR-200 (75)
aR-250
NZMB2-A250
250
C3
37-45
gG-63 (37)
gG-100 (45)
gG-150
NZMB2-A200
150
C4
55-75
aR-160 (55)
aR-200 (75)
aR-250
NZMB2-A250
250
Table 3.9 525-600 V, Frame Sizes B and C
UL Compliance
Fuses or circuit breakers are mandatory to comply with NEC 2009. Danfoss recommends using a selection of the following.
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240 V, 480 V, 500 V, or
600 V depending on the unit's voltage rating. With the proper fusing, the frequency converter’s Short Circuit Current Rating
(SCCR) is 100,000 Arms.
Recommended max. fuse
Power
[kW]
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
11
KTN-R-80
JKS-80
JJN-80
-
-
-
15-18.5
KTN-R-125
JKS-125
JJN-125
-
-
-
22
KTN-R-150
JKS-150
JJN-150
-
-
-
30
KTN-R-200
JKS-200
JJN-200
-
-
-
37
KTN-R-250
JKS-250
JJN-250
-
-
-
Table 3.10 200-240 V, Frame Sizes B and C
Recommended max. fuse
Power
[kW]
SIBA
Littel fuse
Ferraz-
Shawmut
Ferraz-
Shawmut
Type RK1
Type RK1
Type CC
Type RK1
11
5014006-080
KLN-R-80
-
A2K-80-R
15-18.5
2028220-125
KLN-R-125
-
A2K-125-R
22
2028220-150
KLN-R-150
-
A2K-150-R
30
2028220-200
KLN-R-200
-
A2K-200-R
37
2028220-250
KLN-R-250
-
A2K-250-R
Table 3.11 200-240 V, Frame Sizes B and C
How to Install
Operating Instructions
MG34M422
Danfoss A/S © Rev. 2013-07-03 All rights reserved.
31
3
3