13-01 Start Event
Select the boolean (TRUE or FALSE) input to activate Smart Logic
Control.
Option:
Function:
[47]
Up key
[
▲
] is pressed.
[48]
Down key
[
▼
] is pressed.
[50]
Comparator 4
Use the result of comparator 4.
[51]
Comparator 5
Use the result of comparator 5.
[60]
Logic rule 4
Use the result of logic rule 4.
[61]
Logic rule 5
Use the result of logic rule 5.
[94]
RS Flipflop 0
See parameter group
13-1* Comparators
[95]
RS Flipflop 1
See parameter group
13-1* Comparators
[96]
RS Flipflop 2
See parameter group
13-1* Comparators
[97]
RS Flipflop 3
See parameter group
13-1* Comparators
[98]
RS Flipflop 4
See parameter group
13-1* Comparators
[99]
RS Flipflop 5
See parameter group
13-1* Comparators
[100] RS Flipflop 6
See parameter group
13-1* Comparators
[101] RS Flipflop 7
See parameter group
13-1* Comparators
13-02 Stop Event
Select the boolean (TRUE or FALSE) input to deactivate Smart
Logic Control.
Option:
Function:
[0]
FALSE
For descriptions [0]-[61], see
Start
Event
[1]
TRUE
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current Limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10]
Out of speed range
[11]
Below speed low
[12]
Above speed high
[13]
Out of feedb. range
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
[17]
Mains out of range
[18]
Reverse
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
13-02 Stop Event
Select the boolean (TRUE or FALSE) input to deactivate Smart
Logic Control.
Option:
Function:
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[30]
SL Timeout 0
[31]
SL Timeout 1
[32]
SL Timeout 2
[33]
Digital input DI18
[34]
Digital input DI19
[35]
Digital input DI27
[36]
Digital input DI29
[37]
Digital input DI32
[38]
Digital input DI33
[39]
Start command
[40]
Drive stopped
[41]
Reset Trip
[42]
Auto-reset Trip
[43]
OK key
[44]
Reset key
[45]
Left key
[46]
Right key
[47]
Up key
[48]
Down key
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
[70]
SL Timeout 3
Smart Logic Controller timer 3 is
timed out.
[71]
SL Timeout 4
Smart Logic Controller timer 4 is
timed out.
[72]
SL Timeout 5
Smart Logic Controller timer 5 is
timed out.
[73]
SL Timeout 6
Smart Logic Controller timer 6 is
timed out.
[74]
SL Timeout 7
Smart Logic Controller timer 7 is
timed out.
[75]
Start command given
[76]
Digital input x30/2
[77]
Digital input x30/3
[78]
Digital input x30/4
[79]
Digital input x46/1
Parameter Descriptions
Operating Instructions
MG34M422
Danfoss A/S © Rev. 2013-07-03 All rights reserved.
87
6
6