Terminal 37 is suitable for category 3 installations according to EN 954-1 (safe stop according to category 0 EN 60204-1) as
required by the EU Machinery Directive 98/37/EC. Terminal 37 and the Safe Stop function are designed in conformance with
EN 60204-1, EN 50178, EN 61800-2, EN 61800-3, and EN 954-1. For correct and safe use of the Safe Stop function follow the
related information and instructions in the Application Guidelines.
Analog Inputs
Number of analog inputs
2
Terminal number
53, 54
Modes
Voltage or current
Mode select
Switch S201 and switch S202
Voltage mode
Switch S201/switch S202 = OFF (U)
Voltage level
-10 to +10 V (scaleable)
Input resistance, Ri: approx
10 k
Ω
Max. voltage
± 20 V
Current mode
Switch S201/switch S202 = ON (I)
Current level
0/4 to 20 mA (scaleable)
Input resistance, Ri
approx. 200
Ω
Max. current
30 mA
Resolution for analog inputs
10 bit (+ sign)
Accuracy of analog inputs
Max. error 0.5% of full scale
Bandwidth
100 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Digital Output
Programmable digital/pulse outputs
2
Terminal number
27, 29
1)
Voltage level at digital/frequency output
0-24 V
Max. output current (sink or source)
40 mA
Max. load at frequency output
1 k
Ω
Max. capacitive load at frequency output
10 nF
Minimum output frequency at frequency output
0 Hz
Maximum output frequency at frequency output
32 kHz
Accuracy of frequency output
Max. error: 0.1 % of full scale
Resolution of frequency outputs
12 bit
1)
Terminal 27 and 29 can also be programmed as input. The digital output is galvanically isolated from the supply voltage
(PELV) and other high-voltage terminals.
General Specifications