Digital input function
Select
Terminal
Ramp bit 0
[34]
All
Ramp bit 1
[35]
All
Mains failure inverse
[36]
All
Day/night control
[39]
All
DigiPot Increase
[55]
All
DigiPot Decrease
[56]
All
DigiPot Clear
[57]
All
Counter A (up)
[60]
29, 33
Counter A (down)
[61]
29, 33
Reset Counter A
[62]
All
Counter B (up)
[63]
29, 33
Counter B (down)
[64]
29, 33
Reset Counter B
[65]
All
Lead pump start
[120]
All
Lead pump alternation
[121]
All
Comp. 1 Interlock
[130]
All
Comp. 2 Interlock
[131]
All
Comp. 3 Interlock
[132]
All
Comp. 1 Inv. interlock
[139]
All
Comp. 2 Inv. interlock
[140]
All
Comp. 3 Inv. interlock
[141]
All
Table 6.4 Overview of Digital Inputs
Functions dedicated to only one digital input are stated in the associated parameter.
All digital inputs can be programmed to these functions:
[0]
No
operation
No reaction to signals transmitted to the
terminal.
[1]
Reset
Resets frequency converter after a TRIP/ALARM.
Not all alarms can be reset.
[2]
Coast
inverse
(Default Digital input 27): Coasting stop,
inverted input (NC). The frequency converter
leaves the motor in free mode. Logic ‘0’
⇒
coasting stop.
[3]
Coast and
reset
inverse
Reset and coasting stop Inverted input (NC).
Leaves motor in free mode and resets
frequency converter. Logic ‘0’
⇒
coasting stop
and reset.
[4]
Quick stop
inverse
Inverted input (NC). Generates a stop in
accordance with quick-stop ramp time set in
parameter 3-81 Quick Stop Ramp Time
. When
motor stops, the shaft is in free mode. Logic ‘0’
⇒
Quick-stop.
[5]
DC-brake
inverse
Inverted input for DC braking (NC). Stops
motor by energizing it with a DC current for a
certain time period. See
parameter 2-01 DC
Brake Current
to
parameter 2-03 DC Brake Cut In
Speed [RPM]
. The function is only active when
the value in
parameter 2-02 DC Braking Time
is
different from 0. Logic ’0’
⇒
DC braking.
[6]
Stop
inverse
Stop Inverted function. Generates a stop
function when the selected terminal goes from
logical level ‘1’ to ‘0’. The stop is performed
according to the selected ramp time
(
parameter 3-42 Ramp 1 Ramp Down Time
,
parameter 3-52 Ramp 2 Ramp Down Time
,
parameter 3-62 Ramp 3 Ramp down Time
,
parameter 3-72 Ramp 4 Ramp Down Time
).
NOTICE!
When the frequency converter is at the
torque limit and has received a stop
command, it may not stop by itself. To
ensure that the frequency converter
stops, configure a digital output to
[27]
Torque limit & stop
and connect this
digital output to a digital input that is
configured as coast.
[8]
Start
(Default Digital input 18): Select start for a
start/stop command. Logic ‘1’ = start, logic ‘0’
= stop.
[9]
Latched
start
The motor starts, if a pulse is applied for min.
2 ms. The motor stops when Stop inverse is
activated.
[10] Reversing
(Default Digital input 19). Change the direction
of motor shaft rotation. Select Logic ‘1’ to
Parameter Descriptions
Operating Instructions
MG34M422
Danfoss A/S © Rev. 2013-07-03 All rights reserved.
63
6
6