Mains Supply (L1, L2, L3)
Supply voltage
200-240 V ±10%
Supply voltage
380-480 V ±10%
Supply voltage
525-600 V ±10%
Supply frequency
50/60 Hz
Max. imbalance temporary between mains phases
3.0 % of rated supply voltage
True Power Factor (λ)
≥ 0.9 nominal at rated load
Displacement Power Factor (cos φ) near unity
(> 0.98)
Switching on input supply L1, L2, L3 (power-ups) ≤ 7.5 kW
Max. 2 times/min.
Switching on input supply L1, L2, L3 (power-ups) ≥ 11 kW
Max. 1 time/min.
Environment according to EN60664-1
Overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 240/500/600
V maximum
Motor Compressor Output (U, V, W)
Output voltage
0-100% of supply voltage
Switching on output
See
parameter 14-01 Switching Frequency
Cable lengths and cross sections
Max. motor cable length, screened/armored
150 m
Max. motor cable length, unscreened/unarmored
300 m
Max. cross section to motor, mains, load sharing and brake *
Maximum cross section to control terminals, rigid wire
1.5 mm
2
/16 AWG (2 x 0.75 mm
2
)
Maximum cross section to control terminals, flexible cable
1 mm
2
/18 AWG
Maximum cross section to control terminals, cable with enclosed core
0.5 mm
2
/20 AWG
Minimum cross section to control terminals
0.25 mm
2
* See Table 8.1, Table 8.2 and Table 8.3 for more information!
Digital Inputs
Voltage level
0 - 24 V DC
Voltage level, logic.0. PNP
< 5 V DC
Voltage level, logic.1. PNP
> 10 V DC
Voltage level, logic .0. NPN2)
> 19 V DC
Voltage level, logic .1. NPN2)
< 14 V DC
Maximum voltage on input
28 V DC
Input resistance, Ri
approx. 4 k
Ω
Safe Stop Terminal 37
Voltage level
0 - 24 V DC
Voltage level, logic.0. PNP
< 4 V DC
Voltage level, logic.1. PNP
>20 V DC
Nominal input current at 24 V
50 mA
rms
Nominal input current at 20 V
60 mA
rms
Input capacitance
400 nF
Terminal 37 is fixed PNP logic
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1.
Terminals 27 and 29 can also be programmed as output.
2.
Except safe stop input Terminal 37.
3.
Terminal 37 can only be used as safe stop input.
General Specifications
VLT
®
Compressor Drives CDS 302/CDS 303
164
Danfoss A/S © Rev. 2013-07-03 All rights reserved.
MG34M422
8
8