Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
s]
Upeak
[kV]
dU/dt
[kV/
μ
s]
36
480
0.312
2.846
100
480
0.556
1.250
1.798
150
480
0.608
1.230
1.618
Table 6.26 P18KT4
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
s]
Upeak
[kV]
dU/dt
[kV/
μ
s]
15
480
0.288
3.083
100
480
0.492
1.230
2.000
150
480
0.468
1.190
2.034
Table 6.27 P22KT4
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
s]
Upeak
[kV]
dU/dt
[kV/
μ
s]
5
480
0.368
1.270
2.853
50
480
0.536
1.260
1.978
100
480
0.680
1.240
1.426
150
480
0.712
1.200
1.334
Table 6.28 P30KT4
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
s]
Upeak
[kV]
dU/dt
[kV/
μ
s]
5
480
0.368
1.270
2.853
50
480
0.536
1.260
1.978
100
480
0.680
1.240
1.426
150
480
0.712
1.200
1.334
Table 6.29 P37KT4
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
s]
Upeak
[kV]
dU/dt
[kV/
μ
s]
15
480
0.256
1.230
3.847
50
480
0.328
1.200
2.957
100
480
0.456
1.200
2.127
150
480
0.960
1.150
1.052
Table 6.30 P45KT4
380-500 V (T5)
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
s]
Upeak
[kV]
dU/dt
[kV/
μ
s]
5
480
0.371
1.170
2.523
Table 6.31 P55KT5
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
s]
Upeak
[kV]
dU/dt
[kV/
μ
s]
5
480
0.371
1.170
2.523
Table 6.32 P75KT5
600 V (T6)
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
s]
Upeak
[kV]
dU/dt
[kV/
μ
s]
36
600
0.304
1.560
4.105
50
600
0.300
1.550
4.133
100
600
0.536
1.640
2.448
150
600
0.576
1.640
2.278
Table 6.33 P15KT6
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
s]
Upeak
[kV]
dU/dt
[kV/
μ
s]
36
600
0.084
1.560
7.962
50
600
0.120
1.540
5.467
100
600
0.165
1.472
3.976
150
600
0.190
1.530
3.432
Table 6.34 P30KT6
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
s]
Upeak
[kV]
dU/dt
[kV/
μ
s]
15
600
0.276
1.184
4.290
Table 6.35 P75KT6
525-690 V (T7)
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
s]
Upeak
[kV]
dU/dt
[kV/
μ
s]
80
690
0.58
1.728
2369
130
690
0.93
1.824
1569
180
690
0.925
1.818
1570
Table 6.36 P7K5T7
Cable
length [m]
Mains
voltage
[V]
Rise time
[
μ
s]
Upeak
[kV]
dU/dt
[kV/
μ
s]
6
690
0.238
1416
4739
50
690
0.358
1764
3922
150
690
0.465
1872
3252
Table 6.37 P45KT7
Product Specifications
VLT
®
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
80
MG33BF02 - Rev. 2013-12-20
6
6