Recommended max. fuse
Power
[kW]
Max.
prefuse
Bussmann
E52273
RK1/JDDZ
Bussmann
E4273
J/JDDZ
Bussmann
E4273
T/JDDZ
SIBA
E180276
RK1/JDDZ
LittelFuse
E81895
RK1/JDDZ
Ferraz-
Shawmut
E163267/E2137
RK1/JDDZ
Ferraz-
Shawmut
E2137
J/HSJ
11
30 A
KTS-R-30
JKS-30
JKJS-30
5017906-030
KLS-R-030
A6K-30-R
HST-30
15-18.5
45 A
KTS-R-45
JKS-45
JJS-45
5014006-050
KLS-R-045
A6K-45-R
HST-45
22
60 A
KTS-R-60
JKS-60
JJS-60
5014006-063
KLS-R-060
A6K-60-R
HST-60
30
80 A
KTS-R-80
JKS-80
JJS-80
5014006-080
KLS-R-075
A6K-80-R
HST-80
37
90 A
KTS-R-90
JKS-90
JJS-90
5014006-100
KLS-R-090
A6K-90-R
HST-90
45
100 A
KTS-R-100
JKS-100
JJS-100
5014006-100
KLS-R-100
A6K-100-R
HST-100
55
125 A
KTS-R-125
JKS-125
JJS-125
2028220-125
KLS-150
A6K-125-R
HST-125
75
150 A
KTS-R-150
JKS-150
JJS-150
2028220-150
KLS-175
A6K-150-R
HST-150
Table 9.16 525-690 V,Enclosure Types B and C
Electrical Installation
VLT
®
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
MG33BF02 - Rev. 2013-12-20
131
9