6.1.4 Mains Supply 525-690 V (FC 302 only)
Type Designation
P1K1
P1K5
P2K2
P3K0
P4K0
P5K5
P7K5
High/Normal Overload
1)
HO/NO
HO/NO
HO/NO
HO/NO
HO/NO
HO/NO
HO/NO
Typical Shaft output (kW)
1.1
1.5
2.2
3.0
4.0
5.5
7.5
Enclosure IP20
A3
A3
A3
A3
A3
A3
A3
Output current
Continuous (525-550V) [A]
2.1
2.7
3.9
4.9
6.1
9.0
11.0
Intermittent (525-550V) [A]
3.4
4.3
6.2
7.8
9.8
14.4
17.6
Continuous (551-690V) [A]
1.6
2.2
3.2
4.5
5.5
7.5
10.0
Intermittent (551-690V) [A]
2.6
3.5
5.1
7.2
8.8
12.0
16.0
Continuous KVA 525 V
1.9
2.5
3.5
4.5
5.5
8.2
10.0
Continuous KVA 690 V
1.9
2.6
3.8
5.4
6.6
9.0
12.0
Max. input current
Continuous (525-550V) [A]
1.9
2.4
3.5
4.4
5.5
8.1
9.9
Intermittent (525-550V) [A]
3.0
3.9
5.6
7.0
8.8
12.9
15.8
Continuous (551-690V) [A]
1.4
2.0
2.9
4.0
4.9
6.7
9.0
Intermittent (551-690V) [A]
2.3
3.2
4.6
6.5
7.9
10.8
14.4
Additional specifications
Max. cable cross-section
4)
for mains, motor, brake and
load sharing [mm
2
] ([AWG])
4, 4, 4 (12, 12, 12) (min. 0.2 (24)
Max. Cable cross-section
4)
for disconnect [mm
2
]
([AWG])
6, 4, 4 (10, 12, 12)
Estimated power loss at rated max. load (W)
3)
44
60
88
120
160
220
300
Efficiency
2)
0.96
0.96
0.96
0.96
0.96
0.96
0.96
Table 6.10 A3 Enclosure, Mains Supply 525-690 V IP20/Protected Chassis, P1K1-P7K5
Type Designation
P11K
P15K
P18K
P22K
High/Normal Overload
1)
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft output at 550 V [kW]
7.5
11
11
15
15
18.5
18.5
22
Typical Shaft output at 690 V [kW]
11
15
15
18.5
18.5
22
22
30
Enclosure IP20
B4
B4
B4
B4
Enclosure IP21, IP55
B2
B2
B2
B2
Output current
Continuous (525-550V) [A]
14.0
19.0
19.0
23.0
23.0
28.0
28.0
36.0
Intermittent (60 s overload) (525-550V) [A]
22.4
20.9
30.4
25.3
36.8
30.8
44.8
39.6
Continuous (551-690V) [A]
13.0
18.0
18.0
22.0
22.0
27.0
27.0
34.0
Intermittent (60 s overload) (551-690V) [A]
20.8
19.8
28.8
24.2
35.2
29.7
43.2
37.4
continuous KVA (at 550 V) [KVA]
13.3
18.1
18.1
21.9
21.9
26.7
26.7
34.3
continuous KVA (at 690 V) [KVA]
15.5
21.5
21.5
26.3
26.3
32.3
32.3
40.6
Max. input current
Continuous (at 550 V) (A)
15.0
19.5
19.5
24.0
24.0
29.0
29.0
36.0
Intermittent (60 s overload) (at 550 V) (A)
23.2
21.5
31.2
26.4
38.4
31.9
46.4
39.6
Continuous (at 690 V) (A)
14.5
19.5
19.5
24.0
24.0
29.0
29.0
36.0
Intermittent (60 s overload) (at 690 V) (A)
23.2
21.5
31.2
26.4
38.4
31.9
46.4
39.6
Additional specifications
Max. cable cross-section
4)
for mains/motor, load
share and brake [mm
2
] ([AWG])
35, 25, 25 (2, 4, 4)
Max cable cross-section
4)
for mains disconnect
[mm
2
] ([AWG])
16,10,10 (6, 8, 8)
Estimated power loss at rated max. load (W)
3)
150
220
220
300
300
370
370
440
Efficiency
2)
0.98
0.98
0.98
0.98
Table 6.11 B2/B4 Enclosure, Mains Supply 525-690 V IP20/IP21/IP55 - Chassis/NEMA 1/NEMA 12 (FC 302 only), P11K-P22K
Product Specifications
VLT
®
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
66
MG33BF02 - Rev. 2013-12-20
6
6