Type Designation
P37K
P45K
P55K
P75K
High/Normal Overload
1)
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft Output [kW]
37
45
45
55
55
75
75
90
Enclosure IP20
C3
C3
C3
C4
C4
Enclosure IP21, IP55, IP66
C1
C1
C1
C2
C2
Output current
Continuous (525-550 V) [A]
54
65
65
87
87
105
105
137
Intermittent (525-550 V) [A]
81
72
98
96
131
116
158
151
Continuous (551-600 V) [A]
52
62
62
83
83
100
100
131
Intermittent (551-600 V) [A]
78
68
93
91
125
110
150
144
Continuous kVA (550 V) [kVA]
51.4
61.9
61.9
82.9
82.9
100.0
100.0
130.5
Continuous kVA (575 V) [kVA]
51.8
61.7
61.7
82.7
82.7
99.6
99.6
130.5
Max. input current
Continuous at 550 V [A]
49
59
59
78.9
78.9
95.3
95.3
124.3
Intermittent at 550 V [A]
74
65
89
87
118
105
143
137
Continuous at 575 V [A]
47
56
56
75
75
91
91
119
Intermittent at 575 V [A]
70
62
85
83
113
100
137
131
Additional specifications
IP20 max. cable cross-section for mains and motor
[mm
2
] ([AWG])
50 (1)
150 (300 MCM)
IP20 max. cable cross-section for brake and load
sharing [mm
2
] ([AWG])
50 (1)
95 (4/0)
IP21, IP55, IP66 max. cable cross-section for mains and
motor [mm
2
] ([AWG])
50 (1)
150 (300 MCM)
IP21, IP55, IP66 max. cable cross-section for brake and
load sharing [mm
2
] ([AWG])
50 (1)
95 (4/0)
Max cable cross-section
4)
for mains disconnect [mm
2
]
([AWG])
50, 35, 35
(1, 2, 2)
95, 70, 70
(3/0, 2/0, 2/0)
185, 150, 120
(350MCM,
300MCM, 4/0)
Estimated power loss at rated max. load [W]
3)
740
900
900
1100
1100
1500
1500
1800
Efficiency
2)
0.98
0.98
0.98
0.98
Table 6.9 Mains Supply 525-600 V (FC 302 only), P37K-P75K
Product Specifications
VLT
®
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
MG33BF02 - Rev. 2013-12-20
65
6
6