Type Designation
P11K
P15K
P18K
P22K
P30K
High/Normal Overload
1)
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft Output [kW]
11
15
15
18.5
18.5
22
22
30
30
37
Enclosure IP20
B3
B3
B4
B4
B4
Enclosure IP21, IP55, IP66
B1
B1
B2
B2
C1
Output current
Continuous (525-550 V) [A]
19
23
23
28
28
36
36
43
43
54
Intermittent (525-550 V) [A]
30
25
37
31
45
40
58
47
65
59
Continuous (551-600 V) [A]
18
22
22
27
27
34
34
41
41
52
Intermittent (551-600 V) [A]
29
24
35
30
43
37
54
45
62
57
Continuous kVA (550 V) [kVA]
18.1
21.9
21.9
26.7
26.7
34.3
34.3
41.0
41.0
51.4
Continuous kVA (575 V) [kVA]
17.9
21.9
21.9
26.9
26.9
33.9
33.9
40.8
40.8
51.8
Max. input current
Continuous at 550 V [A]
17.2
20.9
20.9
25.4
25.4
32.7
32.7
39
39
49
Intermittent at 550 V [A]
28
23
33
28
41
36
52
43
59
54
Continuous at 575 V [A]
16
20
20
24
24
31
31
37
37
47
Intermittent at 575 V [A]
26
22
32
27
39
34
50
41
56
52
Additional specifications
IP20 max. cable cross-section
4)
for
mains, brake, motor and load
sharing [mm
2
] ([AWG])
10, 10,- (8, 8,-)
10, 10,- (8, 8,-)
35,-,-(2,-,-)
35,-,-(2,-,-)
35,-,-(2,-,-)
IP21, IP55, IP66 max. cable cross-
section
4)
for mains, brake and load
sharing [mm
2
] ([AWG])
16, 10, 10 (6, 8, 8) 16, 10, 10 (6, 8, 8)
35,-,-(2,-,-)
35,-,-(2,-,-)
50,-,- (1,-,-)
IP21, IP55, IP66 max. cable cross-
section
4)
for motor [mm
2
] ([AWG])
10, 10,- (8, 8,-)
10, 10,- (8, 8,-)
35, 25, 25 (2, 4, 4) 35, 25, 25 (2, 4, 4)
50,-,- (1,-,-)
Max. cable cross-section
4)
for
Disconnect [mm
2
] ([AWG])
16, 10, 10
(6, 8, 8)
50, 35, 35
(1, 2, 2)
Estimated power loss
at rated max. load [W]
3)
220
300
300
370
370
440
440
600
600
740
Efficiency
2)
0.98
0.98
0.98
0.98
0.98
Table 6.8 Mains Supply 525-600 V (FC 302 only), P11K-P30K
Product Specifications
VLT
®
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
64
MG33BF02 - Rev. 2013-12-20
6
6