6.2 General Specifications
6.2.1 Mains Supply
Mains supply
Supply Terminals (6-Pulse)
L1, L2, L3
Supply voltage
200-240 V
±
10%
Supply voltage
FC 301: 380-480 V/FC 302: 380-500 V
±
10%
Supply voltage
FC 302: 525-600 V
±
10%
Supply voltage
FC 302: 525-690 V
±
10%
Mains voltage low/mains drop-out:
During low mains voltage or a mains drop-out, the frequency converter continues until the intermediate circuit voltage drops
below the minimum stop level, which corresponds typically to 15% below the frequency converter's lowest rated supply voltage.
Power-up and full torque cannot be expected at mains voltage lower than 10% below the frequency converter's lowest rated
supply voltage.
Supply frequency
50/60 Hz
±
5%
Max. imbalance temporary between mains phases
3.0 % of rated supply voltage
True Power Factor (
λ
)
≥
0.9 nominal at rated load
Displacement Power Factor (cos
ϕ
)
near unity (
>
0.98)
Switching on input supply L1, L2, L3 (power-ups)
≤
7.5 kW
maximum 2 times/min.
Switching on input supply L1, L2, L3 (power-ups) 11-75 kW
maximum 1 time/min.
Switching on input supply L1, L2, L3 (power-ups)
≥
90 kW
maximum 1 time/2 min.
Environment according to EN60664-1
overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240/500/600/690
V maximum.
6.2.2 Motor Output and Motor Data
Motor output (U, V, W)
Output voltage
0-100% of supply voltage
Output frequency
0-590 Hz
3)
Output frequency in Flux Mode
0-300 Hz
Switching on output
Unlimited
Ramp times
0.01-3600 s
Torque characteristics
Starting torque (constant torque)
maximum 160% for 60 s
1)
once in 10 min.
Starting/overload torque (variable torque)
maximum 110% up to 0.5 s
1)
once in 10 min.
Torque rise time in FLUX (for 5 kHz fsw)
1 ms
Torque rise time in VVC
+
(independent of fsw)
10 ms
1) Percentage relates to the nominal torque.
2) The torque response time depends on application and load but as a general rule, the torque step from 0 to reference is 4-5 x
torque rise time.
3) Special customer versions with output frequency 0-1000 Hz are available.
Product Specifications
VLT
®
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
68
MG33BF02 - Rev. 2013-12-20
6