4.1.3 Missing Motor Phase Detection
The Missing Motor Phase Function (
4-58 Missing Motor
Phase Function
) is enabled by default to avoid motor
damage in the case that a motor phase is missing. The
default setting is 1,000 ms, but it can be adjusted for a
faster detection.
4.1.4 Mains Phase Imbalance Detection
Operation under severe main imbalance conditions
reduces the lifetime of the motor. Conditions are
considered severe if the motor is operated continuously
near nominal load. The default setting trips the frequency
converter in case of mains imbalance (
14-12 Function at
Mains Imbalance
).
4.1.5 Switching on the Output
Adding a switch to the output between the motor and the
frequency converter is permitted. Fault messages may
appear. Enable flying start to catch a spinning motor.
4.1.6 Overload Protection
Torque Limit
The torque limit feature protects the motor against
overload, independent of the speed. Torque limit is
controlled in
4-16 Torque Limit Motor Mode
and or
4-17 Torque Limit Generator Mode
and the time before the
torque limit warning trips is controlled in
14-25 Trip Delay
at Torque Limit
.
Current Limit
The current limit is controlled in
4-18 Current Limit
and the
time before the frequency converter trips is controlled in
14-24 Trip Delay at Current Limit
.
Speed Limit
Min. speed limit:
4-11 Motor Speed Low Limit [RPM]
or
4-12 Motor Speed Low Limit [Hz]
limit the operating speed
range to for instance between 30 and 50/60Hz.
Max. speed limit: (
4-13 Motor Speed High Limit [RPM]
or
4-19 Max Output Frequency
limit the max output speed the
frequency converter can provide.
ETR
ETR is an electronic feature that simulates a bimetal relay
based on internal measurements. The characteristic is
shown in
Voltage Limit
The inverter turns off to protect the transistors and the
intermediate circuit capacitors when a certain hard-coded
voltage level is reached.
Overtemperature
The frequency converter has built-in temperature sensors
and reacts immediately to critical values via hard-coded
limits.
4.1.7 Locked Rotor Protection
There may be situations when the rotor is locked due to
excessive load or some other factors (bearing, or
application create locked rotor situation). This leads to
overheating of motor winding (free movement of rotor is
required for proper cooling). The frequency converter is
able to detect the locked rotor situation with open loop
PM flux control, and PM VVC
+
control (
30-22 Locked Rotor
Protection
).
4.1.8 Automatic Derating
The frequency converter constantly checks for critical
levels:
•
Critical high temperature on the control card or
heatsink
•
High motor load
•
High DC-link voltage
•
Low motor speed
As a response to a critical level, the frequency converter
adjusts the switching frequency. For critical high internal
temperatures and low motor speed, the frequency
converters can also force the PWM pattern to SFAVM.
NOTICE
The automatic derating is different when
14-55 Output
Filter
is set to
[2] Sine-Wave Filter Fixed
.
4.1.9 Automatic Energy Optimisation
Automatic energy optimisation (AEO), directs the frequency
converter to continuously monitor the load on the motor
and adjust the output voltage to maximise efficiency.
Under light load, the voltage is reduced and the motor
current is minimised. The motor benefits from increased
efficiency, reduced heating, and quieter operation. There is
no need to select a V/Hz curve because the frequency
converter automatically adjusts motor voltage.
4.1.10 Automatic Switching Frequency
Modulation
The frequency converter generates short electrical pulses
to form an AC wave pattern. The carrier frequency is the
rate of these pulses. A low carrier frequency (slow pulsing
rate) causes noise in the motor, making a higher carrier
frequency preferable. A high carrier frequency, however,
generates heat in the frequency converter which can limit
the amount of current available to the motor. The use of
insulated gate bi-polar transistors (IGBT) means very high-
speed switching.