8.2 Mechanical Dimensions
Enclosure Type
A1
A2
A3
A4
A5
B1
B2
B3
B4
Power
[kW]
200-240 V
0.25–1.5
0.25-2.2
3-3.7
0.25-2.2
0.25-3.7
5.5-7.5
11
5.5-7.5
11-15
380-480/500 V 0.37-1.5
0.37-4.0
5.5-7.5
0.37-4
0.37-7.5
11-15
18.5-22
11-15
18.5-30
525-600 V
0.75-7.5
0.75-7.5
11-15
18.5-22
11-15
18.5-30
525-690 V
1.1-7.5
11-22
11-30
Illustrations
130BA870.10
130BA809.10
130BA810.10
130BB458.10
130BA811.10
130BA812.10
130BA813.10
130BA826.10
130BA827.10
IP
20
20
21
20
21
55/66
55/66
21/55/66 21/55/66
20
20
NEMA
Chassis Chassis Type 1 Chassis Type 1
Type
12/4X
Type
12/4X
Type
1/12/4X
Type
1/12/4X
Chassis
Chassis
Height [mm]
Height of back
plate
A
200
268
375
268
375
390
420
480
650
399
520
Height with de-
coupling plate for
Fieldbus cables
A
316
374
-
374
-
-
-
-
-
420
595
Distance between
mounting holes
a
190
257
350
257
350
401
402
454
624
380
495
Width [mm]
Width of back
plate
B
75
90
90
130
130
200
242
242
242
165
230
Width of back
plate with one C
option
B
-
130
130
170
170
-
242
242
242
205
230
Width of back
plate with 2 C
options
B
-
150
150
190
190
-
242
242
242
225
230
Distance between
mounting holes
b
60
70
70
110
110
171
215
210
210
140
200
Depth [mm]
Depth without
option A/B
C
207
205
207
205
207
175
200
260
260
249
242
With option A/B
C
222
220
222
220
222
175
200
260
260
262
242
Screw holes [mm]
c
6.0
8.0
8.0
8.0
8.0
8.25
8.25
12
12
8
-
d
ø8
ø11
ø11
ø11
ø11
ø12
ø12
ø19
ø19
12
-
e
ø5
ø5.5
ø5.5
ø5.5
ø5.5
ø6.5
ø6.5
ø9
ø9
6.8
8.5
f
5
9
9
6.5
6.5
6
9
9
9
7.9
15
Max weight [kg]
2.7
4.9
5.3
6.6
7.0
9.7
13.5/14.2
23
27
12
23.5
Front cover tightening torque [Nm]
Plastic cover (low IP)
Click
Click
Click
-
-
Click
Click
Click
Click
Metal cover (IP55/66)
-
-
-
1.5
1.5
2.2
2.2
-
-
C
a
b
130BA648.12
f
e
B
A
a
d
e
b
c
a
e
f
130BA715.12
Illustration 8.1 Top and Bottom Mounting Holes
(B4, C3 and C4 only)
Table 8.1 Mechanical Dimensions, Enclosure Types A and B
Mechanical Installation
VLT
®
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
108
MG33BF02 - Rev. 2013-12-20
8
8