Function:
Setting of the desired operating mode when the
mains voltage is reconnected.
Description of choice:
Auto restart
[0] is selected if the frequency converter is to
start up in the same start/stop condition as immediately
before power to the frequency converter is cut off.
OFF/Stop
[1] is selected if the frequency converter
is to remain stopped when the mains voltage is
connected, until a start command is active. To
restart, activate the key [HAND START] or [AUTO
START] by using the control panel.
NB!:
If [HAND START] or [AUTO START] cannot
be activated by the keys on the control
panel (see parameter 012/014
Hand/Auto
start on LCP)
the motor will not be able to
restart if
OFF/Stop
[1] is selected. If Handstart
or Autostart has been programmed for activation
via the digital inputs, the motor will not be able
to restart if
OFF/Stop
[1] is selected.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port