VLT
®
8000 AQUA
Non UL compliance
If UL/cUL is not to be complied with, we recommend the above mentioned fuses or:
VLT 8006-8032
200-240 V
type gG
VLT 8042-8062
200-240 V
type gR
VLT 8006-8072
380-480 V
type gG
VLT 8102-8122
380-480 V
type gR
VLT 8152-8352
380-480 V
type gG
VLT 8452-8652
380-480 V
type gR
VLT 8002-8072
525-600 V
type gG
Not following the recommendation may result
in damage of the drive in case of malfunction.
Fuses must be designed for protection in a circuit
capable of supplying a maximum of 100000 A
rms
(symmetrical), 500 V /600 V maximum.