VLT
®
8000 AQUA
Programming
309 Terminal 53, min. scaling
(AI 53 SCALE LOW)
Value:
0.0 - 10.0 V
✭
0.0 V
Function:
This parameter is used for setting the signal value
that has to correspond to the minimum reference
or the minimum feedback, parameter 204
Minimum
reference, Ref
MIN
/413
Minimum feedback, FB
MIN
. See
Reference handling
or
Feedback handling
.
Description of choice:
Set the required voltage value.
For reasons of accuracy, voltage losses in long
signal lines can be compensated for.
If the time-out function is to be applied (parameters
317
Time out
and 318
Function after time out
),
the value must be set to > 1 V.
310 Terminal 53, max. scaling
(AI 53 SCALE HIGH)
Value:
0.0 - 10.0 V
✭
10.0 V
Function:
This parameter is used for setting the signal value that
has to correspond to the maximum reference value
or the maximum feedback, parameter 205
Maximum
reference, Ref
MAX
/414
Maximum feedback, FB
MAX
.
See
Reference handling
or
Feedback handling
.
Description of choice:
Set the required voltage value.
For reasons of accuracy, voltage losses in long
signal lines can be compensated for.
311 Terminal 54, analog input voltage
(AI [V] 54 FUNCT.)
Value:
See description of parameter 308.
✭
No operation
Function:
This parameter chooses between the different functions
available for the input, terminal 54.
Scaling of the input signal is done in parameter
312
Terminal 54, min. scaling
and in parameter
313
Terminal 54, max. scaling
.
Description of choice:
See description of parameter 308.
For reasons of accuracy, voltage losses in long
signal lines should be compensated for.
312 Terminal 54, min. scaling
(AI 54 SCALE LOW)
Value:
0.0 - 10.0 V
✭
0.0 V
Function:
This parameter is used for setting the signal value
that corresponds to the minimum reference value or
the minimum feedback, parameter 204
Minimum
reference, Ref
MIN
/413
Minimum feedback, FB
MIN
.
See
Reference handling
or
Feedback handling
.
Description of choice:
Set the required voltage value.
For reasons of accuracy, voltage losses in long
signal lines can be compensated for.
If the time-out function is to be applied (parameters
317
Time out
and 318
Function after time ou
t),
the value must be set to > 1 V.
313 Terminal 54, max. scaling
(AI 54 SCALE HIGH)
Value:
0.0 - 10.0 V
✭
10.0 V
Function:
This parameter is used for setting the signal value
that corresponds to the maximum reference value
or the maximum feedback, parameter 204
Minimum
reference, Ref
MIN
/414
Maximum feedback, FB
MAX
. See
Reference handling
or
Feedback handling
.
Description of choice:
Set the required voltage value.
For reasons of accuracy, voltage losses in long
signal lines can be compensated for.
314 Terminal 60, analog input current
(AI [MA] 60 FUNCT.)
Value:
See description of parameter 308.
✭
Reference
Function:
This parameter allows a choice between the
different functions available for the input, terminal
60. Scaling of the input signal is done in parameter
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.83.A2.02 - VLT is a registered Danfoss trademark
123