
VLT
®
8000 AQUA
Installation
■
Technical data, mains supply 3 x 525 - 690 V
According to international requirements
VLT type 8502
8602
8652
Output current
I
VLT,N
[A] (525-550 V) 523
596
630
I
VLT, MAX
(60 s) [A] (525-550 V) 575
656
693
I
VLT,N
[A] (551-690 V) 500
570
630
I
VLT, MAX
(60 s) [A] (551-690 V) 550
627
693
Output power
S
VLT,N
[kVA] (550 V) 498
568
600
S
VLT,N
[kVA] (575 V) 498
568
627
S
VLT,N
[kVA] (690 V) 598
681
753
Typical shaft output (525-550 V) P
VLT,N
[kW]
500
560
630
Typical shaft output (551-690 V) P
VLT,N
[HP]
400
500
600
Max. cable cross-section to motor and DC-bus [mm
2
]
4) 5)
4 x 240
4 x 240
4 x 240
Max. cable cross-section to motor and DC-bus [AWG]
2)
4) 5)
4 x 500 mcm
4 x 500 mcm
4 x 500 mcm
I
L,MAX
[A] (550 V) 504
574
607
I
L,MAX
[A] (575 V) 482
549
607
Max.
input
current (RMS)
I
L,MAX
[A] (690 V) 482
549
607
Max. cable cross-section to power [mm
2
]
4) 5)
4 x 240
4 x 240
4 x 240
Max. cable cross-section to power [AWG]
2) 4) 5)
4 x 500 mcm
4 x 500 mcm
4 x 500 mcm
Max. pre-fuses
(mains)
[-]/UL [A]
1 )
700/700
900/900
900/900
Efficiency
3)
0.98
0.98
0.98
Weight IP 00/
Chassis
[kg/lbs] 221/488
236/520
277/611
Weight IP 20/
NEMA 1
[kg/lbs] 263/580
272/600
313/690
Weight IP 54/
NEMA 12
[kg/lbs] 263/580
272/600
313/690
Power loss at
max. load
[W] 7249
8727
9673
Enclosure
IP 00/Chassis/IP 21/NEMA 1/IP 54/NEMA 12
1. For type of fuse, see section
Fuses
.
2. American Wire Gauge.
3. Measured using 30 m/100 ft screened motor cables at rated load and rated frequency.
4. Always comply with national and local regulations on min. cable cross-section. Max. cable cross section
is the maximum possible cable cross section that can be fitted on the terminals.
5. Connection bolt, power supply, motor and load sharing: M10 (compression lug), 2 x M8 (box lug)
MG.83.A2.02 - VLT is a registered Danfoss trademark
47